Input terminal function assignment
Using Pr. 178 to Pr. 182, set the functions of the input terminals.
Refer to the following table and set the parameters:
Setting
Signal
Pr. 59 = 0 (initial value)
0
RL
Pr. 59 ≠ 0 ∗1
Pr. 59 = 0 (initial value)
1
RM
Pr. 59 ≠ 0 ∗1
Pr. 59 = 0 (initial value)
2
RH
Pr. 59 ≠ 0 ∗1
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
External thermal relay input ∗2
7
OH
8
REX
15-speed selection (combination with three speeds RL, RM, RH)
10
X10
Inverter run enable signal (FR-HC, FR-CV connection)
12
X12
PU operation external interlock
14
X14
PID control valid terminal
PU/External operation switchover (turning ON X16 selects External
16
X16
operation)
18
X18
V/F switchover (V/F control is performed when X18 is ON)
24
MRS
Output stop
25
STOP
Start self-holding selection
60
STF
Forward rotation command (assigned to STF terminal (Pr. 178) only) —
61
STR
Reverse rotation command (assigned to STR terminal (Pr. 179) only) —
62
RES
Inverter reset
PU/NET operation switchover (turning ON X65 selects PU
65
X65
operation)
External/NET operation switchover (turning ON X66 selects NET
66
X66
operation)
Command source switchover (turning ON X67 makes Pr. 338 and Pr.
67
X67
339 commands valid)
9999
No function
∗1
When Pr. 59 Remote function selection ≠ "0", the functions of the RL, RM and RH signals are changed as given in the table.
∗2
The OH signal turns ON when the relay contact "opens".
NOTE
Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the X10 signal (FR-HC, FR-CV connection-inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned with Pr.79 Operation mode selection set to "7", the MRS signal shares this
function.
Same signal is used to assign multi-speed (7 speeds) and remote setting. These cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same
time.)
When V/F control is selected by V/F switchover (X18 signal), second function is also selected at the same time.
Control between V/F and General-purpose magnetic flux can not be switched during operation. In case control is
switched between V/F and General-purpose magnetic flux, only second function is selected.
Turning the AU signal ON makes terminal 2 (voltage input) invalid.
(2)
Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
Function assignment of external terminal and control
Function
Low-speed operation command
Remote setting (setting clear)
Middle-speed operation command
Remote setting (deceleration)
High-speed operation command
Remote setting (acceleration)
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr.232 to Pr.239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 44 to Pr. 51
Pr. 267
Pr. 15, Pr. 16
Pr. 9
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 30, Pr. 70
Pr. 79
Pr. 127 to Pr. 134
Pr. 79, Pr. 340
Pr. 80
Pr. 17
Pr. 79, Pr. 340
Pr. 79, Pr. 340
Pr. 338, Pr. 339
Refer to
Page
90
94
90
94
90
94
117
151
92
101
90
111
166
211
172
76, 106
116
118
118
118
173
173
175
4
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents