Bias And Gain Of Frequency Setting Voltage (Current) (Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) To C7 (Pr. 905)) - Mitsubishi Electric FR-D720-0.1K Instruction Manual

Hide thumbs Also See for FR-D720-0.1K:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 2, 4)
4.16.3 Bias and gain of frequency setting voltage (current)
(Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) to C7 (Pr. 905))
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0 to
5VDC, 0 to 10VDC or 4 to 20mADC).
Set Pr. 267 and voltage/current input switch to switch among 0 to 5VDC, 0 to 10VDC, and 0 to 20mADC input using
terminal 4. (Refer to page 151)
[Frequency setting bias/gain parameter]
Parameter
Number
Terminal 2 frequency setting
125
gain frequency
Terminal 4 frequency setting
126
gain frequency
Analog input display unit
241 ∗1, ∗3
switchover
C2 (902)
Terminal 2 frequency setting
∗1, ∗2
bias frequency
C3 (902)
Terminal 2 frequency setting
∗1, ∗2
bias
C4 (903)
Terminal 2 frequency setting
∗1, ∗2
gain
C5 (904)
Terminal 4 frequency setting
∗1, ∗2
bias frequency
C6 (904)
Terminal 4 frequency setting
∗1, ∗2
bias
C7 (905)
Terminal 4 frequency setting
∗1, ∗2
gain
∗1
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 163)
∗2
The parameter number in parentheses is the one for use with the operation panel (PA02) for the FR-E500 series or parameter unit (FR-PU04/FR-PU07).
∗3
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
154
Initial
Name
Value
60Hz
60Hz
0
0Hz
0%
100%
0Hz
20%
100%
Setting
Range
0 to 400Hz
Frequency of terminal 2 input gain (maximum).
0 to 400Hz
Frequency of terminal 4 input gain (maximum).
0
Displayed in %
1
Displayed in V/mA
0 to 400Hz
Frequency on the bias side of terminal 2 input.
Converted % of the bias side voltage of terminal 2
0 to 300%
input.
Converted % of the gain side voltage of terminal 2
0 to 300%
input.
0 to 400Hz
Frequency on the bias side of terminal 4 input.
Converted % of the bias side current (voltage) of
0 to 300%
terminal 4 input.
Converted % of the gain side current (voltage) of
0 to 300%
terminal 4 input.
Description
Unit for analog input display.