INSTALLATION GUIDELINE FR-D740-012(SC) to 160(SC)-EC FR-D720S-008(SC) to 100(SC)-EC Thank you for choosing this Mitsubishi Electric Inverter. Please read through this Installation Guideline and the CD-ROM enclosed to operate this inverter correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions.
Page 2
This Installation Guideline provides handling information and precautions for use of the equipment. Please forward this Installation Guideline to the end user. 2. Fire Prevention This section is specifically about safety matters CAUTION Do not attempt to install, operate, maintain or inspect the ...
Page 3
The electronic thermal relay function does not guarantee protection of the motor from overheating. It is iodine, etc.) infiltrate into a Mitsubishi Electric product, recommended to install both an external thermal and PTC the product will be damaged. Halogenbased materials are thermistor for overheat protection.
1 PRODUCT CHECKING AND PARTS IDENTIFICATION Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. Inverter model - EC D740...
Page 5
PRODUCT CHECKING AND PARTS IDENTIFICATION General Precaution The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power OFF, wait for more than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock. Environment ...
WIRING 3 WIRING Terminal connection diagram (Sink-logic safety terminal model) Source logic 1. DC reactor (FR-HEL) When connecting a DC reactor, remove the Main circuit terminal jumper across P1 and P/+. Control circuit terminal Single-phase power input Brake unit *6 A brake transistor is not built-in to the (Option) FR-D720S-008 and 014.
Page 8
WIRING Terminal connection diagram (Source-logic safety terminal model) Source logic 1. DC reactor (FR-HEL) When connecting a DC reactor, remove the Main circuit terminal jumper across P1 and P/+. Control circuit terminal Single-phase power input Brake unit *6 A brake transistor is not built-in to the (Option) FR-D720S-008SC and 014SC.
Page 9
WIRING Main circuit terminal specifications 3.3.1 Terminal arrangement of the main circuit terminal, power supply and the motor wiring Three-phase 400V class FR-D740-012(SC) to 080(SC) FR-D740-120(SC), 160(SC) Screw size (M4) Jumper Jumper R/L1 S/L2 T/L3 N/- P/+ Screw size (M4) R/L1 S/L2 T/L3 P/+ PR Screw size...
Page 10
WIRING 3.3.2 Cables and wiring length (1) Cable size and other specifications of the main circuit terminals and the earthing terminal Select the recommended cable size to ensure that a voltage drop will be 2% or less. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
Page 11
WIRING (2) Total wiring length The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below. 200V class Pr. 72 PWM frequency selection setting (carrier frequency) or Higher 1 (1kHz) or less 200m 200m 300m...
Page 12
WIRING Control circuit specifications (1) Control circuit terminal layout Recommended wire size: 0.3mm to 0.75mm RUN SE S1 S2 SC STF STR (2) Wiring method Wiring Use a blade terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of the wire and apply directly.
Page 13
WIRING 3) Insert the wire into a socket. When using a single wire or stranded wire without a blade terminal, push an open/ close button all the way down with a flathead screw driver, and insert the wire. Open/close button Flathead screwdriver Note ...
Provide a common mode choke on the output side of the inverter. (This is effective regardless of the use of the capacitive filter.) Mitsubishi Electric capacitive filter: FR-BIF, SF[], FR-E5NF-[], FR-S5NFSA[], FR-BFP2-[] ® Recommended common mode choke: FT-3KM F series FINEMET common mode choke cores manufactured by Hitachi Metals, Ltd.
Page 15
PRECAUTIONS FOR USE OF THE INVERTER (11) Do not use the inverter input side magnetic contactor to start/stop the inverter. Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000 times), frequent starts and stops of the MC must be avoided.
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi Electric assures best quality...
PARAMETER LIST 6 PARAMETER LIST For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the operation panel.
Page 18
PARAMETER LIST Initial Initial Name Setting Range Name Setting Range Value Value 0, 0.1 to 5s, 0.1 to 1000%, Restart coasting time 9999 PID proportional band 100% 9999 9999 Restart cushion time 0 to 60s 0.1 to 3600s, PID integral time Remote function selection 0, 1, 2, 3 9999...
Page 19
PARAMETER LIST Initial Initial Name Setting Range Name Setting Range Value Value Monitor decimal digits 0, 1, 3, 4, 7, 8, 0, 1, 9999 9999 selection 11 to 16, 25, 26, RUN terminal function Parameter for manufacturer setting. Do not set. 46, 47, 64, 70, selection Magnitude of frequency...
Page 20
PARAMETER LIST Initial Differ according to capacities. Name Setting Range Value 6%: FR-D740-022(SC) or lower, FR-D720S-042(SC) or lower 4%: FR-D740-036(SC) to 080(SC), FR-D720S-070(SC) and 100(SC) Amplitude acceleration time 0.1 to 3600s 3%: FR-D740-120(SC) and 160(SC) Differ according to capacities. Amplitude deceleration time 0.1 to 3600s 5s: FR-D740-080(SC) or lower, FR-D720S-008(SC) to 100(SC)
TROUBLESHOOTING 7 TROUBLESHOOTING When a fault occurs in the inverter, the inverter output is shut off and the PU display automatically changes to one of the following fault or alarm indications. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative.
Page 22
TROUBLESHOOTING List of fault or alarm indications Operation Panel Indication Name Operation Panel Indication Name E.ILF Input phase loss E--- Fault history HOLD Operation panel lock E.OLT Stall prevention stop E. BE Brake transistor alarm detection Er1 to 4 Parameter write error Output side earth (ground) fault E.GF...
Page 23
CE marking. The authorized representative in the EU The authorized representative in the EU is shown below. Name: Mitsubishi Electric Europe B.V. Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany (1) EMC Directive We declare that this inverter, when equipped with the EMC Directive compliant EMC filter, conforms with the EMC Directive and affix the CE marking on the inverter.
Page 24
(2) Low Voltage Directive We have self-confirmed our inverters as products compliant to the Low Voltage Directive and affix the CE marking on the inverters. Low Voltage Directive: 2014/35/EU Standard: EN61800-5-1:2007 Outline of instructions Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth. Connect the equipment to the earth securely.
Page 25
When you set the electronic thermal relay protection function dedicated to the Mitsubishi Electric constant-torque motor, this characteristic curve applies to operation at 6Hz or higher. 105% 52.5% (For selection of the operation characteristic, refer to Chapter 4 of the Instruction Manual.)
Page 26
Manufacturer Model Rated Voltage, Vac MMP-T32 Mitsubishi Electric Corp. 480Y/277 Suitable for use in a circuit capable of delivering not more than 50 or 25 kA rms symmetrical amperes, 480Y/277 volts maximum when protected by the Type E combination motor controllers indicated in the above table.
Page 27
4. Short circuit ratings 200V class • Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 264V maximum. 400V class • Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 528V maximum. 5.
Page 28
The SERIAL number (refer to Appendix 3) can be checked on the rating plate (refer to page 1) of the product. • Authorized sales representative (importer) in the CU area The authorized sales representative (importer) in the CU area is shown below. Name: Mitsubishi Electric (Russia) LLC Address: 52, bld 1 Kosmodamianskaya Nab 115054, Moscow, Russia Phone: +7 (495) 721-2070...
Page 29
Appendix 6 Referenced Standard (Requirement of Chinese standardized law) This Product is designed and manufactured accordance with following Chinese standards. Machinery safety : GB/T 16855.1 GB/T 12668.502 GB 28526 GB 12668.3 Electrical safety : GB 12668.501 : GB 12668.3 ...
Page 30
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi Electric. (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi Electric products. (3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other than Mitsubishi Electric products.
Page 32
The copyright and other rights of the enclosed CD-ROM all belong to Mitsubishi Electric Corporation. No part of the enclosed CD-ROM may be copied or reproduced without the permission of Mitsubishi Electric Corporation. Specifications of the enclosed CD-ROM are subject to change for modification without notice.
Page 33
REVISIONS *The manual number is given on the bottom left of the back cover. Revision Date Revision Manual Number Dec. 2007 IB-0600352ENG-A First edition Mar. 2008 IB-0600352ENG-B Modification Introduced products on bar terminals Apr. 2008 IB-0600352ENG-C Addition • FR-D720S-008 to 100 Jun.
Page 34
5, Mavrogenous Str. SE- 223 55 Lund GR-18542 Piraeus Phone: +46 (0) 8 625 10 00 Phone: +30 (0)211 / 1206-900 Mitsubishi Electric Turkey Elektrik Ürünleri A.Ş. TURKEY Fax: +30 (0)211 / 1206-999 Fabrika Otomasyonu Merkezi MELTRADE Kft. HUNGARY Şerifali Mahallesi Nutuk Sokak No.5 Fertő...
Need help?
Do you have a question about the FR-D740-012SC-EC and is the answer not in the manual?
Questions and answers