Mitsubishi Electric FR-D720-0.1K Instruction Manual page 211

Hide thumbs Also See for FR-D720-0.1K:
Table of Contents

Advertisement

Parameter
Parameter
Register
41000 to
Refer to the parameter list (page
0 to 999
41999
58) for the parameter names.
Terminal 2 frequency setting
C2(902)
41902
bias frequency
Terminal 2 frequency setting bias
42092
(Analog value)
C3(902)
Terminal 2 frequency setting bias
43902
(Terminal analog value)
Terminal 2 frequency setting gain
125(903)
41903
frequency
Terminal 2 frequency setting gain
42093
(Analog value)
C4(903)
Terminal 2 frequency setting gain
43903
(Terminal analog value)
Terminal 4 frequency setting bias
C5(904)
41904
frequency
Terminal 4 frequency setting bias
42094
(Analog value)
C6(904)
Terminal 4 frequency setting bias
43904
(Terminal analog value)
Terminal 4 frequency setting
126(905)
41905
gain frequency
Terminal 4 frequency setting gain
42095
(Analog value)
C7(905)
Terminal 4 frequency setting gain
43905
(Terminal analog value)
Frequency setting voltage bias
C22(922)
41922
frequency (built-in
potentiometer)
Frequency setting voltage bias
C23(922)
42112
(built-in potentiometer)
Frequency setting voltage gain
C24(923)
41923
frequency (built-in
potentiometer)
Frequency setting voltage gain
C25(923)
42113
(built-in potentiometer)
Faults history
Register
Definition
40501
Fault history 1
40502
Fault history 2
40503
Fault history 3
40504
Fault history 4
40505
Fault history 5
40506
Fault history 6
40507
Fault history 7
40508
Fault history 8
Fault code list
Data
Definition
No fault
H00
present
H10
E.OC1
H11
E.OC2
H12
E.OC3
H20
E.OV1
H21
E.OV2
H22
E.OV3
H30
E.THT
* Refer to page 255 for details of fault description.
Communication operation and setting
Parameter Name
Read/write
Read/write
Read/write The analog value (%) set to C3 (902) is read.
Read/write
Read/write The analog value (%) set to C4 (903) is read.
Read/write
Read/write The analog value (%) set to C6 (904) is read.
Read/write
Read/write The analog value (%) set to C7 (905) is read.
Read/write
Read/write The analog value (%) set to C23 (922) is read.
Read/write
Read/write The analog value (%) set to C25(923) is read.
Read/write
Read/write
Read
Read
Read
Read
Read
Read
Read
Data
Definition
Data
H31
E.THM
HB0
H40
E.FIN
HB1
H52
E.ILF
HB2
H60
E.OLT
HC0
H70
E.BE
HC4
H80
E.GF
HC5
H81
E.LF
HC7
H90
E.OHT
HC9
H91
E.PTC
HF5
Read/
Remarks
Write
The parameter number + 41000 is the register
number.
The analog value (%) of the voltage applied to the
Read
terminal 2 is read.
The analog value (%) of the voltage applied to the
Read
terminal 2 is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
Remarks
Being 2 bytes in length, the data is stored as
"H00
".
Refer to the lowest 1 byte for the error code.
Performing write using the register 40501 batch-
clears the faults history.
Set any value as data.
Definition
E.PE
E.PUE
E.RET
E.CPU
E.CDO
E.IOH
E.AIE
E.SAF
E.5
4
209