Mitsubishi Electric FR-D720-0.1K Instruction Manual page 37

Hide thumbs Also See for FR-D720-0.1K:
Table of Contents

Advertisement

Control circuit specifications
(3)
Safety stop function operation
Input signal
Input power
S1-SC
OFF
-----
Short
ON
Open
Short
Open
∗1
At an internal safety circuit fault, E.SAF or E.CPU is displayed on the operation panel.
SA is displayed on the operation panel when both the S1 and S2 signals are in the open state without any internal safety circuit fault (E.SAF, E.CPU).
∗2
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
For more details, refer to the Safety stop function instruction manual (BCN-A211508-000). (Please contact your sales representative
for the manual.)
Do not connect the FR-E700-SC/NC/NF series together with the FR-D700 series. If connected together, the
safety stop function does not work properly.
28
Internal
safety
S2-SC
SAFE
circuit
∗1
---- -
-----
OFF
No failure
OFF
Short
Failure
OFF
No failure
ON
Open
Failure
OFF
Open
N/A
OFF
Short
N/A
OFF
" N/A " denotes a condition where circuit fault does not apply.
Output signal
Inverter operation state
SAFE2
∗2
∗2
OFF
Output shutoff (Safe state)
ON
OFF
Output shutoff (Safe state)
ON
Output shutoff (Safe state)
OFF
Output shutoff (Safe state)
OFF
Output shutoff (Safe state)
OFF
Output shutoff (Safe state)
CAUTION
Drive enabled