DT4260 xx xx xx xx
Area of application
20111006-V0

3.3. Principle of operation

The DT4260 xx xx xx xx AC Current Meter enable
0-1 AAC / 0-5 AAC current ranges to be displayed on the
control panel. Large 14.2 mm height LED display make
process value easily visible at a distance. The displayed
value is proportional to the True RMS value of the input
current.
The input current to be measured should be connected to
the instrument's input shunt through a current transformer.
Easy on-site configuration through the front panel
membrane keypad is a major advantage of the
microcontroller-based technology. The configuration
parameters: input range, current transformer ratio, signal
filtering, output scaling, display refresh rate, limit modes,
limit values, etc. are stored in EEPROM. The settings are
protected by a two-level password against unauthorized
manipulation.
Options:
Two normally open relay contacts (SPST) for limit
switching or for simple control tasks.
4-20 mA / 0-20 mA galvanic isolated scalable analogue
output. The output can be active (A) or passive (P).
RS232 galvanic isolated communication output with
MODBUS RTU slave protocol. Only one instrument can be
connected to the PLC or to the computer.
RS485 galvanic isolated communication output with
MODBUS RTU slave protocol. 32 instrument can be
connected to the PLC or to the computer.
Note: either analogue or communication option can be
implemented at the same time.