Sequence of operations 1. Enter the menu with the supervisor code.
20220103-V2
7.7. The temperature value belonging to the 4 mA value
(05 menu item)
The apparatus regulates the loop current between 4 and 20
mA in proportion with the measured temperature.
In this menu item any ºC values between -200,0 ºC and
600,0 ºC could be assigned to the 4 mA loop current.
[Factory default setting: -200,0 ºC]
Attention! In addition to selecting the temperature value
assigned to 4 mA, also the temperature value to be
assigned to 20 mA must be selected (The next menu item).
Read chapter 7.1. Writing the code in to see how the
code should be written in. On the display you see this:

.
2. Keep stepping with the ▲ button as long as you see this

menu item:
3. Enter the menu item by using the ENTER button.

4. The number
blinking. The blinking digit indicates which of the digits is
selected. The selection can be modified by using the ▲
button.
6. Using the ► button you can go to the next digit.
7. By using the ▲ button, you can increase the value of the
blinking digit:




,
,
,
,
8. If you have selected the last digit (the digit on the right
side), and you press the ► button, a blinking colon will
appear on the left side:
that the positive or negative sign is being selected, and you
can now change it by the ▲ button.
9. With the ▲ button you can switch the negative sign on
or off.

= 200,0 ºC

= -200,0 ºC
.
is visible on the display. Digit 2 is





,
,
,
,
,

. This colon indicates,
, etc.