Intrinsically safe temperature meter / transmitter
Table of Contents

Advertisement

86
Example for the practical usage of the limit outputs
Task:
The limit output No.1 should control a heater, that switches
ON when the temperature goes lower than 70 ºC, and
switches OFF when it goes higher than 90 ºC.
The limit output No.2 should control a buzzer. The buzzer
should be signalling continuously as long as a manual
acknowledgement takes place, in those cases when the
temperature goes, at any time, lower than 50 ºC, or when it
goes higher than 95 ºC
The settings of the limit outputs are as follows:

operating mode=
temperature is lower than the low limit)

Low limit =

Hysteresis of the low limit =

High limit =

Hysteresis of the high limit =
indifferent)

Alarm mode =

Operating mode=
temperature does not fall between the limits.)

Low limit =

Hysteresis of the low limit =

High limit =

Hysteresis of the high limit =

Alarm mode =

(Switches ON, when the

ºC


ºC (it's value is indifferent)



(Switches ON, when the

ºC


ºC


DT9500
ºC
ºC (it's value is
ºC
ºC
20220103-V2