CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TEST OUTPUT SETS
This function allows you to test one, or all of the system's output sets by altering their state from
Normal to Triggered.
Enter AL3 (4444) > Engineer Functions > Test Output Sets.
When the TEST OUTPUT SETS prompt appears, press the Accept
window will appear.
Output Set : 1
5
6
Press the
and
buttons to select the output set you would like to test (1 to 16 or ALL). Press the
4
Accept
button and the following window will appear:
Output Set : 1 is Normal
Change the state using the Accept button
4
Press the Accept
button and the selected output set will change state from normal to triggered.
Output Set : 1 is Triggered
Change the state using the Accept button
To test additional output sets, press the
number and state.
Finally, press the Escape
When exiting this function the panel will ask for confirmation to reset the outputs to their normal
settings. Press the Accept
TEST SOUNDERS IN GROUPS
This function allows you to test one, or all of the system's sounder groups by altering their state between
Silenced, Intermittent and Continuous.
Enter AL3 (4444) > Engineer Functions > Test Sounders in Groups.
When the TEST SOUNDERS IN GROUPS prompt appears, press the Accept
selection window will appear:
Sounder Group : 1
5
6
Press the
and
scroll buttons to select the sounder group you would like to test (1 to 16 or ALL).
4
Press the Accept
button and the following window will appear:
Sounder Group : 1 is Silenced
Change the state using the Accept button
4
Press the Accept
button to change the state of the selected sounder group between Silenced,
Intermittent and Continuous. Should you want to test additional sounder groups, press the
buttons to change the sounder group's number.
When exiting this function the panel will ask for confirmation to silence the sounders to their normal
settings. Press the Accept
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 40 of 48
5
and
3
button.
4
button to reset the outputs, or the Escape
4
button to reset the sounders, or the Escape
4
button and the output set selection
6
4
and Accept
button to change the output set's
3
3
button maintain the settings.
4
button and the group
5
button maintain the settings.
6
and

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501/caXfp502/ca

Table of Contents