CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CHANGE ADDRESS
This function is used to change device addresses at the panel, therefore saving the use of ladders to
access a device on site.
Note: The CAPROG Handheld Programmer can be used to manually change the address of a device, but
this will also require a loop learn to be carried out.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Change Address.
When the CHANGE ADDRESS prompt is displayed press the Accept
Select which loop (1 or 2) to change an address using the scroll
Note: Loop 1 has been selected in the following example and the following is displayed:
Loop : 1
Enter the address you want to change using the
The device's LED will light and the following is displayed, for example 'Device 8'.
Loop : 1 Device : 8
New Address : 8
Enter the new address of the device using the
4
the Accept
button.
Loop : 1 Device : 8
New Address : 9
In this example the panel will auto-assign address 8 to address 9.
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
Wait until the old address is flashing, address 8 is shown below.
Old Address: '8'
3
Press the Escape
button x 4. The panel will re-learn the loop. Wait for the process to complete and
a brief summary window will appear, similar to the one shown below:
112 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button then press the Escape
When requested by the panel remove the NVM link shown below:
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 28 of 48
4
5
button then press the Accept
Old Address: 1
5
6
and
scroll buttons then press the Accept
5
6
and
scroll buttons, for example 'Device 9', then press
3
button to return the panel to a normal condition.
button.
4
button.
4
button.