Connecting The Analogue Loop To The Main Control Pcb; Conventional Sounder Circuit Wiring - C-TEC CAST XFP Engineering Manual

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

Connecting the analogue loop to the Main Control PCB

One or two analogue loops are provided (model dependent) each capable of supporting up to 255
addressable devices per loop, giving 510 devices for a 2 loop panel.
Each loop should be connected to the Main Control PCB terminals marked: A+, A- (LOOP A OUT) and
B+, B- (LOOP B RETURN), as shown in Fig.5 below. The loop's earth screens should be connected to the
Main Control PCB terminals marked: Eth.
Fig.5 : Typical analogue addressable loop connection (2 loop panel shown)
LOOP 1A (OUT)
RLY1
RLY2
RLY3
Fault
NC C NO
NC C NO
NC C NO
NC C NO
NVM

Conventional sounder circuit wiring

Two conventional sounder circuits are provided. See technical specification (page 48) for circuit
limitations. If a full complement of sounders are to be used, split them equally across both circuits.
A 6k8 end of line (EOL) resistor (provided) MUST be connected at the end of each sounder circuit to
allow the wiring to be monitored. If the sounder circuit is unused, the 6k8 resistor MUST still be fitted
at the panel terminals.
Each sounder circuit should be connected to the Main Control PCB terminals marked: S1+, S1- and S2+,
S2-, as shown in Fig.6 (page 11). Terminate earth screens at the panel's base earth distribution post, as
shown in Fig.6, page 11.
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Analogue Loop 1
+ S1 -
+ S2 -
Eth A+ A-
Main Control
PCB
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 10 of 48
LOOP 1B (RETURN)
Eth B+ B-
Eth A+ A-
Eth B+ B-
Additional Loop 2
Connector
(if required)
THIS
WAY UP
Power Supply
PCB
BAT
FUSE F
3.15 A H
_
+
BAT1
Hint! C-TEC's ActiV Sounder range
are compatible with this fire alarm
panel (available @ www.c-tec.com).
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
N
N
CO
CONN1
CO
CO
CO
CONN1
CO
CO
CO
CO
CO
CONN
O
O
N
N
NN1
NN1
NN1
NN1
NN1
N
N1
N1
N1
N1
N1
N 1
N
N
N1
N1
N1
N
N1
N
N
N1
1
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501/caXfp502/ca

Table of Contents

Save PDF