CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
How to enter access level three
Access level 3 can be entered using two options:
Option 1: By pressing the Menu button, scrolling down to ENTER ACCESS LEVEL 3 menu and
pressing the Accept4button. The following prompt will appear:
Enter Access Level 3 code:
Enter the four-digit code using the
The default code is:
Option 2:
By entering access level 2, selecting ENTER ACCESS LEVEL 3 menu and repeating the
procedure above.
In access level 3, the panel's Silence/Resound Sounders, Control Panel Reset and Investigate buttons
become active and you can:
•
Scroll through any fire or fault conditions, disablements or zones in test
•
Change the entry codes to access levels 2 and 3 from their factory default settings
•
Connect the panel to a compatible PC for system programming
•
Set the panel up to belong to a non-redundant network of eight CAST XFP main panels, or
allow it to have up to eight XFP repeaters connected to it
•
Gain access to a wide range of commissioning functions including AUTO ADDRESS & LOOP LEARN
•
Gain access to a wide range of engineering, test and fault finding functions
•
Display firmware version numbers and PSU statistics
•
Set the time the panel enters/exits day (building occupied) and night (building unoccupied) mode
•
Access the panel's access level 2 menu options as detailed in the panel's separate user manual
(Document No. DFU5020000)
Fitting the panel's NVM link
To allow site-specific changes to be made to the panel's non-volatile memory
(NVM), the NVM 'memory unlock' link MUST be fitted to the Main Control PCB. It is
recommended that you fit this link as a matter of course whenever you are in access
level 3.
REMEMBER TO RE-LOCK THE MEMORY (REMOVE THE LINK) WHEN PROGRAMMING
IS COMPLETE.
Disabling the panel's internal sounder
Note: The disablement of the panel's internal sounder is non-compliant with EN54-2.
To disable the panel's internal sounder (active in fire & fault conditions), remove
PLK5 link at the Main Control PCB.
Additional Main Control PCB Button/Links
RESET Button - Pressing this button will power down the panel and perform a panel
reset and is only used if the panel has 'locked up'.
PLK1 - DO NOT REMOVE THIS LINK.
PLK4 - DO NOT REMOVE THIS LINK.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 19 of 48
5
4
(1)
4 4 4 4
(four presses of the Escape
6
3
(2)
(3)
(4) buttons.
3
button).
NVM
UNLOCK
Fit For
Beeper
PLK5
RESET
Need help?
Do you have a question about the CAST XFP and is the answer not in the manual?