How To Enter Access Level Three; Fitting The Panel's Nvm 'Memory Unlock' Link - C-TEC CAST XFP Engineering Manual

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

How to enter access level three

Access level 3 can be entered using two options:
Option 1: By pressing the Menu button, scrolling down to ENTER ACCESS LEVEL 3 menu and
pressing the Accept4button. The following prompt will appear:
Enter Access Level 3 code:
Enter the four-digit code using the
The default code is:
Option 2:
By entering access level 2, selecting ENTER ACCESS LEVEL 3 menu and repeating the
procedure above.
In access level 3, the panel's Silence/Resound Sounders, Control Panel Reset and Investigate buttons
become active and you can:
Scroll through any fire or fault conditions, disablements or zones in test
Change the entry codes to access levels 2 and 3 from their factory default settings
Connect the panel to a compatible PC for system programming
Set the panel up to belong to a non-redundant network of eight CAST XFP main panels, or
allow it to have up to eight XFP repeaters connected to it
Gain access to a wide range of commissioning functions including AUTO ADDRESS & LOOP LEARN
Gain access to a wide range of engineering, test and fault finding functions
Display firmware version numbers and PSU statistics
Set the time the panel enters/exits day (building occupied) and night (building unoccupied) mode
Access the panel's access level 2 menu options as detailed in the panel's separate user manual
(Document No. DFU5020000)
Fitting the panel's NVM link
To allow site-specific changes to be made to the panel's non-volatile memory
(NVM), the NVM 'memory unlock' link MUST be fitted to the Main Control PCB. It is
recommended that you fit this link as a matter of course whenever you are in access
level 3.
REMEMBER TO RE-LOCK THE MEMORY (REMOVE THE LINK) WHEN PROGRAMMING
IS COMPLETE.
Disabling the panel's internal sounder
Note: The disablement of the panel's internal sounder is non-compliant with EN54-2.
To disable the panel's internal sounder (active in fire & fault conditions), remove
PLK5 link at the Main Control PCB.
Additional Main Control PCB Button/Links
RESET Button - Pressing this button will power down the panel and perform a panel
reset and is only used if the panel has 'locked up'.
PLK1 - DO NOT REMOVE THIS LINK.
PLK4 - DO NOT REMOVE THIS LINK.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 19 of 48
5
4
(1)
4 4 4 4
(four presses of the Escape
6
3
(2)
(3)
(4) buttons.
3
button).
NVM
UNLOCK
Fit For
Beeper
PLK5
RESET