C-TEC CAST XFP Engineering Manual page 33

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE DST ADJUSTMENT
This function (when enabled) allows you to programme the panel's DST (Daylight Saving Time) so it
automatically goes forward one hour on the last Sunday in March and goes back one hour on the first
Sunday in October:
Enter AL3 (4444) > Commissioning Functions > Enable/Disable DST Adjustment.
When the ENABLE/DISABLE DST ADJUSTMENT prompt appears, press the Accept
following window will appear:
Auto DST Time Adjustment is :
Enabled
5
6
Press the
and
buttons to scroll between 'Enabled' and 'Disabled' and Accept
the option.
When requested by the panel fit the NVM link.
3
Press the Escape
button x 3 and when requested by the panel remove the NVM link.
CONFIGURE SOUNDER DISABLEMENTS
Note: The disablement of individual sounder groups is non-compliant with EN54-2.
Note: Changes to this menu option will affect the ENABLE/DISABLE SOUNDERS menu option, see page 36.
This function configures the sounder groups (1 to 16) to be 'Globally' or 'Individually' disabled or
enabled.
Enter AL3 (4444) > Commissioning Functions > Configure Sounder Disablements.
When accepted, two windows 'Globally' and 'Individually' are available by pressing the
scroll buttons:
Sounder Groups can be Disabled/Enabled
Globally
4
Press the Accept
button to make a selection. When requested by the panel fit the NVM link.
3
Press the Escape
button x 3 and when requested by the panel remove the NVM link.
SWAPPED DEVICE DETECTION
Note: This function is only used to enable 'SWAPPED DEVICE DETECTION' mode. Once this mode is
enabled enter 'IDENTIFY LOOP CHANGES' function to identify the swapped devices. See page 31 for
details.
This function allows you to detect swapped loop devices. A fault may have been displayed at the panel
stating 'Loop Configuration Changed on Loop 1' or 'There are Faults on this Zone'.
First ensure the 'SWAPPED DEVICE DETECTION' function is enabled by performing the following
procedure.
Enter AL3 (4444) > Commissioning Functions > Swapped Device Detection.
When the SWAPPED DEVICE DETECTION prompt is displayed, press the Accept
will display the following window:
Enable Swapped Device Detection? No
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 33 of 48
Sounder Groups can be Disabled/Enabled
Individually
4
button and the
4
to button select
5
6
and
4
button. The panel