CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
FIX DUPLICATE ADDRESSES
This function helps to locate and fix devices with duplicate (double) addresses and also activates device
(polling) LEDs.
If there is a duplicate address a fault may have been displayed
at the panel, e.g. 'There are faults on this zone' (see right).
Enter AL3 (4444) > Commissioning Functions > Address Functions > Fix Duplicate Addresses.
When FIX DUPLICATE ADDRESS prompt is accepted, select Loop 1 or 2 and press the Accept
The panel will re-initialise and check the loop. Wait for the re-initialisation process to finish.
Press the Menu button and the LED of the first duplicate address will be lit steady red, also details of
the first duplicate address found will appear, for example:
Loop: 1
Device: 8
New Address: 3 [DUPLICATE?]
The panel will suggest a new address for the duplicate device. Press the Accept
to the new address, or press scroll
The LED of the second duplicate address will now be lit steady red, also details of the second duplicate
address found will appear. The panel will display the following, for example:
Loop: 1
Device: 10
New Address: 8 [ORIGINAL]
The panel will suggest a new address for the original device. Press the Accept
the new address, or press scroll
The panel will confirm there are no duplicate addresses on the loop shown below:
No Duplicate Addresses on the Loop
3
Press the Escape
button x 3 and the panel will force a loop learn on exiting access level 3. Wait for
the loop learn to finish.
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
The typical display shown below will appear:
9 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button and the Escape
Remove the NVM link when requested by the panel shown below:
Remove NVM Un-Lock Link
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 30 of 48
5
6
and
buttons and Accept
5
6
and
buttons and Accept
3
button.
Zone 1: Kitchen
There are faults on this zone
4
button to change
4
button to select the new address.
4
button to change to
4
button to select a new address.
4
button.