C-TEC CAST XFP Engineering Manual page 27

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
REPLACE/ADD DEVICE
This function may be used, for example, to replace a faulty loop device, or add a new loop device.
NB: THIS MENU OPTION HAS TO BE SELECTED BEFORE A LOOP DEVICE IS
REPLACED OR ADDED.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Replace/Add Device.
When the REPLACE/ADD DEVICE prompt is displayed press the Accept
Select which loop (1 or 2) to replace or add a device using the using the scroll
4
the Accept
button.
Note: Loop 1 has been selected in the following example.
Loop : 1
Select the device address using the
Loop : 1 Device : 10
4
Press the Accept
button and the following display appears:
Loop : 1 Device : 10
Waiting for device
Replace or add the selected loop device to an empty base.
The panel will now auto-address the new device as address 10.
Press the Escape
3
button x 3 and the panel will perform a learning process.
Note: If the panel requests the NVM link to be fitted continue onto the following steps.
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
The panel perform a loop learn and the following summary is displayed:
112 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button and the Escape
Remove NVM Un-Lock Link
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 27 of 48
5
6
and
scroll buttons, as shown below:
Note: If you do not want to proceed at this point, you
may exit this function by pressing the Escape
3
button. Remove the NVM link when requested by the panel.
4
button.
5
button then press
3
button.