C-TEC XFP510-32 Installation Manual

32 zone repeater panel

Advertisement

Quick Links

XFP
32 ZONE
REPEATER
PANEL
installation
manual
approved document no. DFU2200502 Rev 1

Advertisement

Table of Contents
loading

Summary of Contents for C-TEC XFP510-32

  • Page 1 32 ZONE REPEATER PANEL installation manual approved document no. DFU2200502 Rev 1...
  • Page 2: Table Of Contents

    XFP 32 ZONE REPEATER PANEL CONTENTS Important Notes ........................3 Basic Overview & Key features ....................4 Installation and wiring ......................4 The fire panel enclosure ..........................4 Removing the lid and base PCBs........................4 Mounting the base to the wall ........................5 Planning the cable layout in the panel ......................5 Mains wiring..............................6 Connecting mains to the Power Supply PCB ....................6 Installing the standby battery supply ......................7...
  • Page 3: Important Notes

    XFP 32 ZONE REPEATER PANEL IMPORTANT NOTES This equipment must only be installed and maintained by a suitably skilled and technically competent person. This equipment is a piece of Class 1 equipment and MUST BE EARTHED. ALWAYS isolate the panel’s mains and battery backup supplies before making connections to its PCBs.
  • Page 4: Basic Overview & Key Features

    XFP 32 ZONE REPEATER PANEL BASIC OVERVIEW & KEY FEATURES A maximum of eight XFP Repeaters (any mix) can be connected to one non-networked XFP main panel (note that the main panel’s Network Comms function must be set to Repeater mode). Each Repeater requires its own dedicated mains power and battery back-up supply.
  • Page 5: Mounting The Base To The Wall

    XFP 32 ZONE REPEATER PANEL • Disconnect the two-way lid/base connecting cable from PL4 on the Main Control PCB. • Carefully remove the four M4 retaining nuts that secure the hinges and lift off the lid. To remove the base PCBs: - •...
  • Page 6: Mains Wiring

    XFP 32 ZONE REPEATER PANEL Mains wiring The requirement for the mains supply to the fire panel is fixed wiring, using three core cable (no less than 1mm and no more than 2.5mm ) or a suitable three conductor system, fed from an isolating switched fused spur, fused at 3A.
  • Page 7: Installing The Standby Battery Supply

    XFP 32 ZONE REPEATER PANEL Installing the standby battery supply Two new, good quality and fully charged 12V 3.2A Hr valve regulated lead acid batteries are required as the emergency stand-by power supply for the panel. The batteries should be connected in series and located in the panel’s enclosure as shown in Fig.
  • Page 8: Technical Specifications

    XFP 32 ZONE REPEATER PANEL TECHNICAL SPECIFICATION Mains supply voltage: 230V a.c. ± 10% 50/60Hz Internal power supply: 27V d.c Nominal Total output current limited to: 3A @ 230V a.c. Supply and battery charger monitored for failure: Yes Batteries monitored for disconnection and failure: Yes Batteries protected against deep discharge: Max.