C-TEC CAST XFP Engineering Manual page 38

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
MONITOR A POINT
This function allows you to view the current analogue status of any point (any addressable device on
the system).
Enter AL3 (4444) > Engineer Functions > Monitor a Point.
When selected, choose the loop number (1 or 2), press the Accept
5
6
4
,
and Accept
buttons to select the device's address.
Loop : 1
The panel will temporarily disable the point in question and return back its analogue values, for
example:
The loop being
monitored
L : 1 D:7 AV:63
F: 0
The fault code for any fault
condition that device may be in
Note 1: The analogue values returned will differ dependent on whether the device is a detector,
manual call point, I/O unit or sounder.
Note 2: The information displayed will assist C-TEC Technical Support to identify the cause of any
problems.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 38 of 48
The device's
The device's
current analogue value
address
(nominally '0')
21:Cal:150
TC: 0x03
The devices's type code
4
button to continue then press the
Loop:1 Device : 7
The device's gain
value

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501/caXfp502/ca

Table of Contents