CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
DISPLAY DATABASE
This function allows you to view the panel's database of loop devices. Available on a loop by loop
basis, the information displayed includes the device's type, address and description (zone and device
text).
Enter AL3 (4444) > Engineer Functions > Display Database.
When the DISPLAY DATABASE prompt is accepted, select the loop number (1 or 2) and press the
4
Accept
button and you will be prompted to enter the device number.
5
6
Press the
and
scroll buttons to select the device address, then press the Accept
Loop : 1
Device : 22
The information that is stored on the database that relates to that address will appear, for example:
Loop : 1
Dev : 22/0: I/O Unit
Zone : 1
In the above example, 'Dev: 22/0' denotes device address '22' and sub-address '0'. Sub-addresses only
apply to I/O units which may have multiple channels and can be configured as both an input and an
output.
You can now press the
Press the Escape
3
button to exit the function.
VERSION NUMBERS
This function allows you to view the current version number of the panel's firmware and to check when
the site's data was last changed.
Enter AL3 (4444) > Engineer Functions > Version Numbers.
When accepted, the following two windows (with details specific to the panel) will scroll in quick
succession. Press the Escape
The version of the
panel's firmware
XFP 13Ann.n
2 loops fitted: CAST Protocol
The number of loops fitted
1 or 2 (Model Dependent)
Matching site data codes, e.g. 48154/48154
and program checksum codes, e.g.
16886/16886, indicate that the panel
is functioning correctly. Mis-matched
numbers, e.g. 48154/40286, indicate that
the panel's memory may be corrupt.
The information displayed will assist C-TEC
Technical Support to identify the cause of
any problems.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 45 of 48
Gents Toilet
5
6
and
buttons to scroll through the rest of the loop device database.
button to exit the function.
3
The date the panel's
firmware was released
nn/nn/nnnn BL:2A1
The panel's protocol
Bootloader Version
4
button.