C-TEC CAST XFP Engineering Manual page 35

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENGINEER FUNCTIONS
Selecting this menu option takes you to the ENGINEER FUNCTIONS menu. As a rule, pressing the
3
Escape
button when in a submenu will return you to the ENGINEER FUNCTIONS menu.
RESTART THE LOOP
This function may be used, for example, if there is a problem with a missing device, or a device not
closing its s/c isolator.
Enter AL3 (4444) > Engineer Functions > Restart the Loop.
When selected, chose the loop to restart (1 or 2 or ALL) using the
4
the Accept
button. A window similar to the one below will appear:
Restarting loop...
The panel will power down the loop, re-initialize the loop devices and automatically return to the
ENGINEER FUNCTIONS menu.
SET/CLEAR DISABLEMENTS
Selecting this menu option takes you to the disablements submenu which allows you to enable/disable
zones, sounders, outputs, relays, loop devices, the panel's fault relay and output delays.
Any disablement(s) will be indicated at all access levels via the DISPLAY DISABLEMENTS menu option
and the General Disablement LED on the front of the panel.
CAUTION: IT IS STRONGLY RECOMMENDED THAT ALL DISABLEMENTS ARE REGULARLY
REVIEWED AND IMMEDIATELY ENABLED WHEN NO LONGER NECESSARY AS THEY CAN
HAVE A MAJOR AFFECT ON HOW THE SYSTEM WORKS.
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, etc., and may be used to
temporarily disable a zone of devices in areas such as loading bays that are prone to nuisance triggering
from vehicle fumes.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Zones.
When selected, press the Accept
Zone: 1: Loading Bay
Enabled
Select the zone (1 to 32 or ALL) to be disabled/enabled using the
the Accept4button and the zone's status (Enabled or Disabled) will flash. Next, press the
scroll buttons to toggle between enabled and disabled and press the Accept4button to select. The
window will now move to the next available zone allowing further enablements or disablements to be
made. Alternatively, to return to the previous menu press the Escape
Note: If all input devices on a zone have been disabled using the ENABLE/DISABLE DEVICES function
detailed on page 37, the zone they belong to will also be disabled. If you try to re-enable a zone which
has no enabled devices on it, a prompt appears saying this cannot be done. Instead you MUST enable
at least one device on the zone using the ENABLE/DISABLE DEVICES function before re-enabling the
zone itself.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 35 of 48
4
button and a window similar to below will appear:
5
6
and
scroll buttons and press
5
6
and
scroll buttons, then press
3
button.
5
6
and