CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Note: DIP switch (SW1) on the network driver card has no function when used with this panel.
However, all networked CAST XFP main panels require a unique ID number (1 to 8) assigning.
To assign this number and set up network comms, see NETWORK FUNCTIONS page 22 for details.
XFP repeaters DO NOT require an ID number.
Fig.12 : Typical network wiring
The network wiring should be installed to meet BS 5839: Part 1 and BS 7671 (Wiring Regulations) and/or
other national standards of installation where pertinent - see 'cable types & limitations', page 4.
IT IS RECOMMENDED THAT 2-CORE SCREENED, ENHANCED FIRE-RESISTANT CABLE ≥1 MM
NETWORK WIRING.
At each network driver card, connect A to A, B to B and terminate incoming and outgoing screens to
terminal C only as shown below.
At ONE network driver card only, connect A to A, B to B and terminate screens to the panel's base
earth distribution post as shown below.
MAXIMUM NETWORK LENGTH = 1KM
Base
Earth
Distribution
Post
AT ONE PANEL ONLY CONNECT SCREEN
TO THE BASE EARTH DISTRIBUTION POST
(PANEL 1 SHOWN ABOVE)
To Next Networked
Panel (If Required)
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 14 of 48
A
B
C
A
B
CONN1
Panel 1
Network
Driver
Card
(AFP711)
To Next Networked
Panel (If Required)
A
B
C
A
B
CONN1
Panel N
Network
Driver
Card
(AFP711)
FOR OTHER NETWORKED PANELS
DO NOT CONNECT SCREENS TO THE
BASE EARTH DISTRIBUTION POST
2