C-TEC CAST XFP Engineering Manual page 16

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
LED Indicators (continued)
General Fault
Power Supply Fault
System Fault
Sounder Status
Delays Running
Button controls
More Information
5
(Scroll Up)
1
6
(Scroll Down)
3
4
Accept
2
3
Escape
4
Menu
Silence Internal Sounder
Control Panel Reset
Silence / Resound Sounders Silences or resounds the system's sounders (access levels 2 & 3 only)
Investigate
Keyswitch control
I I
O O
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 16 of 48
Flashes yellow when there is a fault condition on the panel. Will always
be lit in conjunction with at least one other fault LED.
Lit yellow when the panel's power supply or mains has failed or the panel's
standby battery is in poor condition.
Lit amber when a system error, such as a microprocessor fault, occurs AND REMAINS
LIT EVEN IF THE SYSTEM FAULT CLEARS. THIS SYSTEM FAULT LED CAN ONLY BE
CLEARED BY PRESSING THE CONTROL PANEL RESET BUTTON AT AL2 OR AL3.
Flashes yellow when a fault is detected on either of the panel's two
conventional sounder circuits or if there is a sounder disablement anywhere on
the system.
Lit yellow when one or more output delays have been programmed by an
engineer. Flashes yellow when one or more output delays are running.
Displays additional information on any fire or fault conditions that appear on
the panel's display. Will also display additional context dependent information
where appropriate.
Dependent on the status of the panel, these two buttons:
• scroll vertically through any fire/fault/disablements/test conditions that
appear on the panel's display
• scroll vertically through the panel's user menus
• select Yes/No in the panel's menu options
• manipulate date, time and disablement settings, etc
• serve as code input buttons to access levels 2 or 3.
Dependent on the status of the panel, these two buttons:
• scroll horizontally through the panel's user menus
• escape or accept options available in the panel's user menus
• serve as code input buttons to access levels 2 or 3.
Provides access to the panel's menus
Silences the panel's internal sounder (also serves as a code input button when
performing a clean start, see page 34)
Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Starts the panel's investigate timer function (access levels 2 & 3 only)
Turning the keyswitch to the armed position 'I' gives the user instant access to
access level 2 (authorised user level). The key is non-removable in position 'I'.