C-TEC CAST XFP Engineering Manual page 39

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TEST DEVICE OUTPUTS
This function allows you to assert the output(s) of an addressable device to check it is working correctly.
It can be used, for example, to assert a detector's LED, or to check that an I/O unit is functioning
correctly. Addressable devices typically may have up to three output channels (LED, Sounder and VAD),
the functions of which depend upon its type, e.g. detector, sounder, manual call point, or I/O unit.
CAUTION: OUTPUT CHANNELS ON AN I/O UNIT MAY BE PROGRAMMED TO TRIGGER SAY,
A WATER EXTINGUISHANT SYSTEM. THIS FUNCTION MUST BE USED WITH EXTREME CARE.
Enter AL3 (4444) > Engineer Functions > Test Device Outputs.
When selected, you will be prompted to enter the loop (1 or 2), device's address and the relevant output:
Loop : 1 Device : 1
Output Bit Value: NONE
5
6
Press the
,
scroll buttons and Accept
(as detailed in the table below).
OUTPUT CHANNELS ASSERTED
None
LED
Sounder
LED & Sounder
VAD
LED & VAD
Sounder & VAD
LED & Sounder & VAD
When you have accepted the required output bit option, the panel will confirm your selection and the
device's output channels will be asserted. If desired, you can now select alternative output channel
5
6
using the
and
scroll buttons.
To exit this function press the Escape
outputs to their normal settings as shown below:
Reset the Outputs?
4
Press the Accept
button to reset the outputs, or the Escape
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 39 of 48
4
button to select the device address and output bit value.
IF YOU ACTIVATE THE OUTPUTS ON MULTIPLE
DEVICES AND THEN EXIT THIS FUNCTION ONLY
THE OUTPUTS ON THE LAST DEVICE SELECTED
WILL AUTO DEACTIVATE. THE REMAINING
OUTPUTS ON WILL STAY ON. THEREFORE,
ENSURE THAT ALL OUTPUTS ARE DE-ACTIVATED
BEFORE EXITING THIS FUNCTION.
3
button x 2. The panel will ask for confirmation to reset the
3
button maintain the settings.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501/caXfp502/ca

Table of Contents