C-TEC CAST XFP Engineering Manual page 34

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
5
Press the scroll
button to select 'Yes'.
Enable Swapped Device Detection? Yes
4
Press the Accept
button.
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
or press ESCape to abort
The panel will update its flash database. Press the Escape
Remove the NVM link when requested by the panel.
Remove NVM Un-Lock Link
To identify the swapped devices, enter IDENTIFY LOOP CHANGES function, see page 31 for details.
CONFIGURE POLLING LED
This function configures the polling (device) LEDs of all loop devices to globally stop flashing during
normal polling. For example, a customer may require polling LEDs to be turned off in a hotel.
Enter AL3 (4444) > Commissioning Functions > Configure Polling LED.
When accepted, the following window will appear:
Blinking LEDs are : Enabled
5
6
Press the
and
buttons to scroll between 'Enabled' and 'Disabled', then press the Accept
to select.
When requested by the panel fit the NVM link. The panel will update the flash database and configure
the loop devices.
3
Press the Escape
button x 3. When requested by the panel remove the NVM link.
MAKE A CLEAN START
CAUTION: USING THIS FUNCTION WILL COMPLETELY ERASE THE PANEL'S DATABASE OF
STORED INFORMATION. THEREFORE, USE THIS FUNCTION WITH EXTREME CARE.
This function allows you to clear the panel's memory back to its factory default settings. Only if you are
confident to proceed, enter the five-digit confirmation code.
Note: The button sequence has to be entered VERY QUICKLY to avoid accidentally erasing panel data.
Enter AL3 (4444) > Commissioning Functions > Make a Clean Start.
The button sequence is:
When requested by the panel fit the NVM link. The panel will erase its record and update the flash database.
3
Press the Escape
button x 3 and remove the NVM link when requested by the panel.
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 34 of 48