Maintenance; Standby Battery Calculation Guide - C-TEC CAST XFP Engineering Manual

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TURN LEDS ON/OFF
This function assists with fault-finding and wiring faults.
Enter AL3 (4444) > Engineer Functions > Turn LEDS ON/OFF.
When accepted, select the loop (1 or 2 or ALL) and panel displays (similar to the following) will appear.
At each display, press the
Options are available to turn the device (polling) LEDS either ON or OFF, at Both Ends/End A Only/End B
Only and the Poll Group (see tables below for device numbers).
Press the Escape
Turn LEDs : OFF
Turn LEDs : Both Ends
CAUTION: ENSURE YOU DO
NOT TURN ON MORE THAN
THREE (3) POLL GROUPS AT
THE SAME TIME, OTHERWISE
TOO MUCH CURRENT WILL
PASS THROUGH THE LOOP.
DIAGNOSTICS FUNCTIONS
These functions are for trained engineers only and are not detailed in this manual. Contact C-TEC
Technical for further assistance.

MAINTENANCE

Periodic system maintenance should be carried out on the system as prescribed in the local design,
maintenance and installation regulations.
The Fire Alarm panel's standby batteries should be checked for integrity of the connections and deposits
indicating venting. A periodic load test with the mains supply disconnected should also be performed
to ensure adequate battery capacity. Both batteries should be renewed if there is any doubt about
their integrity.
The panel's event log should be checked for any faults that have automatically cleared, and these dealt
with accordingly.

STANDBY BATTERY CALCULATION GUIDE

Hint! Hint! An XFP Loop & Battery Calculator Tool is available for download on C-TEC's website
to assist with battery calculations (available @ www.c-tec.com).
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 47 of 48
5
6
and
scroll buttons to toggle, then press the Accept
3
button to exit the function.
Turn LEDs : ON
Poll Group : 0
Poll Group
Device No.
0
1 to 15
1
16 to 31
2
32 to 47
3
48 to 63
4
64 to 79
5
80 to 95
6
96 to 111
7
112 to 127
4
button to proceed.
Poll Group
Device No.
8
128 to 143
9
144 to 159
10
160 to 175
11
176 to 191
12
192 to 207
13
208 to 223
14
224 to 239
15
240 to 255