DATA M A P PI NG

9.2.6. Switching Commands

The following table details the commands that are required from the Master (DCS / PLC) to
be sent to the M10x-M in order to control the motor or feeder module.
Operation
Type
Control Access
Stop
Start
Start CW
Close (CF)
Open (Act)
Start CCW
Close (Close)
Reset

Table 28 Switching Commands sent from DCS to MNS Digital Gateway

1TG C 9 0 8 0 0 4 M 0 2 0 1
Description
Remote control
Bus-Local control
Stop, Open
Start
Start Clockwise
Close for Contactor Feeder applica-
tion
Open for Actuator application
Start Counterclockwise
Close for Actuator Application
Reset
DE FAU LT DATA M AP
Modbus
Remarks
Command
0x2100
M10x-M is controlled
via DCS.
0x2104
DCS allows control via
local HMI.
0x0201
Stops the M10x-M,
Opens contactor K1 for
Contactor Feeder ap-
plication
0x0202
Starts the M10x-M.
Close contactor K1
0x0203
Start the M10x-M
Counterclockwise.
Close contactor K2.
0x1100
Reset of all trips