Wiring; Connectors' Mechanical Connection - Pilz PSSu K F EI CV Operating Manual

Table of Contents

Advertisement

Wiring

6
Wiring
6.1

Connectors' mechanical connection

Please note:
}
The conductor cross section on the spring-loaded terminals without ferrules is 0,2 - 1
mm², 22 - 18 AWG.
}
If you are using multi-core or fine-core cables we recommend ferrules in accordance
with DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm
commend crimping pliers (crimp form A) conforming to EN 60947-1, such as the PZ 6/5
from Weidmüller, for example.
}
Terminal points per connection: 1
}
Stripping length: 8 mm
Operating Manual PSSu K F EI CV(-T)
1004290-EN-04
2
. To crimp the ferrules we re-
43