Operation; Messages - Pilz PSSu K F EI CV Operating Manual

Table of Contents

Advertisement

Operation

7
Operation
7.1

Messages

A module error is displayed via the "Err" LED, signalled to the head module and then
entered in the head module's diagnostic log.
The module can detect the following errors:
Module error
Start-up error
Configuration error
FS communication error
Bus termination error
Temperature error: too warm Ambient temperature too
Output error
Encoder error
Parameter error
Operating Manual PSSu K F EI CV(-T)
1004290-EN-04
Statement
Error as the PSSu system
starts up
Incorrect module type con-
figured.
Error during FS communica-
tion
There is no terminating plate
or there is a bad contact with
the module bus.
high:
Error stack entry/diagnostic
log entry
Error during cyclical output
test for short circuit. Possible
causes: Short circuit, or out-
put defective.
No encoder connected
Incorrect parameter
(Max_Speed or Min_Speed)
Remedy
Change faulty module.
The configured hardware re-
gistry does not match the ac-
tual hardware registry.
Change faulty module.
Install a terminating plate
with integrated end bracket
or insert the base modules
together correctly.
Ensure there is sufficient
ventilation in the control cab-
inet or prevent overload.
Rectify the short circuit or
change the faulty module.
The encoder must be con-
nected correctly
Change the parameter
54

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pssu k f ei cv-t312434314434

Table of Contents