7.2 ELECTRONICS/GENERAL DATA

Control
Method
Output frequency
Performance
V/F control
Vector control
(V V W )
Inputs
Digital
Outputs
Power supply
Safety
Protection
Enclosure
IP00

7.2.1 Considered Standards

Safety
UL 508C - power conversion equipment
standards
UL 840 - insulation coordination including clearances and creepage distances for
electrical equipment
EN61800-5-1 - safety requirements electrical, thermal and energy
EN 50178 - electronic equipment for use in power installations
EN 60204-1 - safety of machinery. Electrical equipment of machines. Part 1: general
requirements
Note: the final assembler of the machine is responsible for installing a safety stop device and a
supply disconnecting device
EN 60146 (IEC 146) - semiconductor converters
EN 61800-2 - adjustable speed electrical power drive systems - part 2: general
requirements
Rating specifications for low voltage adjustable frequency AC power drive systems
Mechanical
EN 60529 - degrees of protection provided by enclosures (IP code)
standards
UL 50 - enclosures for electrical equipment
IEC 60721-3-3 - classification of environmental conditions
26 | ADW300
Table 7.1: Electronics/general data
Types of control:
- V/f (Scalar)
- V V W: voltage vector control
PWM SVM (Space Vector Modulation)
0 to 400 Hz, resolution of 0.1 Hz
Speed regulation: 1 % of the rated speed (with slip
compensation)
Speed variation range: 1:20
Speed regulation: 1 % of the rated speed
Speed variation range: 1:30
4 isolated inputs
Programmable functions
- active low (NPN): maximum low level of 5 Vdc
Maximum input voltage of 30 Vdc
Input current: 11 mA
Maximum input current: 20 mA
5 Vdc power supply. Maximum capacity: 50 mA
Overcurrent/phase-phase short circuit in the output
Under/overvoltage
Motor overload
Overtemperature in the power module (IGBTs)
Fault/external alarm
Programming error
Frame size A
Table 7.2: Considered standards