5.4 PREVENTIVE MAINTENANCE

DANGER!
Always turn off the mains power supply before touching any electrical component
associated to the inverter.
High voltages may still be present even after disconnecting the power supply.
To prevent electric shock, wait at least ten minutes after turning off the input
power for the complete discharge of the power capacitors. Always connect the
equipment frame size to the protective ground (PE). Use the adequate connection
terminal at the inverter.
ATTENTION!
The electronic boards have electrostatic discharge sensitive components.
Do not touch the components or connectors directly. If necessary, first touch the
grounded metallic frame size or wear a ground strap.
Do not perform any withstand voltage test: if necessary, consult WEG.
The inverters require low maintenance when properly installed and operated.
21
presents the main procedures and time intervals for preventive maintenance.
on page 22
provides recommended periodic inspections to be performed every 6 months
after the inverter start-up.
Maintenance
Fan replacement
Electrolytic
If the
capacitors
inverter is
stocked
(not being
used):
"Reforming"
Inverter is
being used:
replace
Table 5.2: Preventive maintenance
Interval
After 40.000 operating hours Replacement
Every year from the
manufacturing date printed
on the inverter identification
label (refer to
Section 2.5
RECEIVING AND STORAGE
on page
5)
Every 10 years
Troubleshooting and Maintenance
Instructions
Apply power to the inverter (voltage between
220 and 230 Vac, single-phase/three-phase or
DC (according to the model of the inverter), 50
or 60 Hz) for at least one hour. Then, disconnect
the power supply and wait at least 24 hours
before using the inverter (reapply power)
Contact WEG technical support to obtain
replacement procedures
Table 5.2 on page
Table 5.3