8.2 ELECTRONICS/GENERAL DATA

CONTROL
PERFORMANCE V/f CONTROL
INPUTS
SAFETY
INTEGRAL
KEYPAD (HMI)
ENCLOSURE
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 8.1: Electronics/general data
METHOD
OUTPUT FREQUENCY
VECTOR CONTROL
(V V W )
DIGITAL
PROTECTION
STANDARD KEYPAD
IP20
Types of control:
- V/f (Scalar);
- V V W: voltage vector control.
PWM SVM (Space Vector Modulation)
0 to 300 Hz, resolution of 0.1 Hz.
Speed regulation: 1 % of the rated speed (with slip
compensation).
Speed variation range: 1:20.
Speed regulation: 1 % of the rated speed.
Speed variation range: 1:30.
4 isolated inputs.
Maximum input voltage of 30 Vdc.
Input current: - 11 mA.
Maximum input current: -20 mA.
Output overcurrent/short-circuit.
Under/overvoltage.
Motor overload.
Overtemperature in the power module (IGBTs).
Fault / external alarm.
Programming error.
4 keys: Start/Stop, Up arrow, Down arrow and Programming.
LCD Display.
View/edition of parameters.
Indication accuracy:
- current: 5 % of the rated current;
- speed resolution: 0.1 Hz.
Frames A, B and C.
Technical Specifications