TIP: Set the relay set and reset point further apart to avoid the
relays from chattering.
Below is what KSONIK MICRO will display on the above applica-
tion. The relay will drive the counter for every 1000 counts. The
analogue output should be approximately 9.82 mA. Relay 2 will set
above 4.76 ft / 1.45 m and reset below 4.43 ft / 1.35 m.
Flow:
T:
Head:
mA Output:
Instant:
Temperature:
Percentage:
12.8

Working with the Simulator

2.46 ft / 0.75 m
Empty distance
16.5 ft / 5.00 m
TIP: Set the relay set and reset point further apart to avoid the
relays from chattering.
In order to activate the simulator proceed with the following:
1. Scroll through the menus with either the
2. Use
to select YES and then press
RUN
3. Press
4. Press
or
Relay 1 will set above 13.3 ft / 4.00 m and reset below 11.55 ft / 3.50 m
Relay 2 will set below 3.28 / 1.00 m and reset above 4.95 ft / 1.50 m.
RUN
5. Press
NOTE: In order for the instrument to go back to normal measurement mode,
go back to the menus and select NO for the Simulate option or reset the
power to the instrument.
K 10
444.60Lt/s
00001513408 Lt
3.28ft.
9.82mA
3.28 ft.
20°C
36.38%
Blanking distance 1.63 ft / 0.50 m
Span 14.85 ft / 4.50 m
SCROLL
to exit the menu.
to start the simulator to increase or decrease the level at the rate of change.
to stop or start the simulator.
SECURITY CODE
MODE
EMPTY DISTANCE
SPAN
BLANKING
RATE OF CHANGE
FAIL TIMER
FAIL SAFE
FLOW UNITS
MAXIMUM FLOW
FLOW CURVE
SETUP RELAYS
RELAY 1
RELAY 1 COUNTER
RELAY 2
RELAY 2 SET
RELAY 2 RESET
TOTALISER RESET
ZERO OFFSET
Set up instrument with the following parameters.
SECURITY CODE
MODE
EMPTY DISTANCE
SPAN
BLANKING
RATE OF CHANGE
SETUP RELAYS
RELAY 1
RELAY 1 SET
RELAY 1 RESET
RELAY 2
RELAY 2 SET
RELAY 2 RESET
or
until the option Simulate appears.
ENTER
ENTER
Level
mA Output:
Instant:
Temperature:
Percentage:
Operation instruction manual | KSONIK MICRO Ultrasonic Level Transmitter 25
5159
FLOW
6.56 ft / 2.00 m
4.92 ft / 1.50 m
1.64 ft / 0.50 m
3.28 ft/min / 1.00 m/min
300
HOLD
Lt/sec
1222
V-NOTCH
YES
Counter
1000
HI
4.76 ft / 1.45 m
4.43 ft / 1.35 m
NO
0
5159
LEVEL
16.5 ft / 5.00 m
14.85 ft / 4.50 m
1.63 ft / 0.50 m
3.28 ft/min / 1.00 m/min
YES
HI
13.2 ft / 4.00 m
11.55 ft / 3.50 m
LO
3.28 ft / 1.00 m
4.95 ft / 1.50 m
K 10
11.55 ft
16.4mA
4.95 ft
20°C
77.77%