Configuration Distance / Level - ABB KSONIK MICRO Operation & Instruction Manual

Ultrasonic level transmitter
Table of Contents

Advertisement

8.0 Configuration Distance / Level
BASIC
SECURITY CODE
MODE
UNITS
EMPTY DISTANCE
SPAN
BLANKING
RATE OF CHANGE
APPLICATION
FACTORY RESET
TEMPERATURE COMPENSATION
SIMULATE
SET PASSWORD
BACKLIGHT
LOSSTIME
LOGTIME
FAILSAFE
FAILSAFE
ENGINEERING UNITS
MAXIMUM VALUE
DECIMAL POINT
ZERO OFF SET
SETUP RELAY
RELAY
SETPOINT
RESET POINT
PUMP CYCLE
CLEAR RELAY
SETUP LINEARISER
ACTIVATE LINEARISER
SETPOINT
HEIGHT
PERCENTAGE
FLOW MODE
OPTIONS
0-9999
DISTANCE/LEVEL/FLOW
METERS/FEET
0.4-15.00 m
0.1-15.00 m
0.3-14.90 m
0.01-20.0 m/min
LIQUIDS/SOLIDS
NO/YES
OFF/ON
NO/YES
NO/YES
OFF/ON (1-60MIN) / PERM
30-900SEC
3.6mA, 4.0mA, 20mA, 21mA, HOLD
3.6mA, 4.0mA, 20mA, 21mA, Hold
NONE, aaa-zzz, AAA-ZZZ,0-9
0-99999
0-3
-50 mm TO 50 mm
NO/YES
OFF/LO/HI
SPAN
SPAN
OFF/FIFO/ROTATE
NO/YES
NO/YES
NO/YES
1-21
0m-SPAN
0-100%
Operation instruction manual | KSONIK MICRO Ultrasonic Level Transmitter 9
DEFAULTS
5159
DISTANCE
METERS
10 m
10 m
0.50 m
1.00 m/min
LIQUIDS
NO
OFF
NO
NO
2 MIN
300SEC
HOLD
Hold
NONE
10000
2
0
NO
OFF
0 m
0 m
OFF
NO
NO
NO
1
0 m
0%