This prompt will allow you to change the default factory code. Should the factory code be forgotten please contact a local
ABB agent for an override password.
DEFAULT No
BACKLIGHT
Choose between switching on the backlight for 1 - 60 minutes, switch off the backlight or to switch the backlight perma-
nently on.
DEFAULT 2 Min
LOSSTIME
This is the amount of time between last receiving a correct echo and going into the Fail-safe condition. This time period
is timed in seconds. This cannot be reduced to less than 30 seconds.
DEFAULT 300 Sec
FAILSAFE
If a loss of echo condition is reached then the 4-20mA output will follow the configured settings 3.60mA, 4mA, 20mA,
21mA or Hold the reading at the last recognized echo. This is usually due to a cable being cut or the instrument not being
set up correctly.
DEFAULT Hold
ENGINEERING UNITS
This prompt will allow you to display in your own engineering units and can be made up from alphanumeric characters.
DEFAULT None
MAXIMUM VALUE/DECIMAL POINT
This is the maximum value the engineering units can be displayed instead of reading meters (m) or feet (ft).
DEFAULT 10000
After the maximum value is set the number of decimal points can be adjusted.
DEFAULT 2
ZERO OFFSET
Choose between –50 mm to 50 mm for setting the offset of the instrument.
DEFAULT 0
SETUP RELAY
Select yes to enter the relay menu and set up the relay parameters.
DEFAULT No
RELAY
The relay can be used either for a high alarm or a low alarm. A high alarm has its reset below the set point, and a low
alarm has its reset above the set point. DEFAULT Off
SET POINT
This is the value where the relay will set.
DEFAULT 0 m
RESET POINT
This is the value where the relay will reset.
DEFAULT 0 m
PUMP CYCLE
Not applicable on this instrument
CLEAR RELAY
Clears the number of cycles as well as the run hours recorded.
DEFAULT No
SETUP LINEARISER
This prompt will allow you to input a curve to linearise the vessel. The span is divided by 21 and you can input the new
Operation instruction manual | KSONIK MICRO Ultrasonic Level Transmitter 11