Use In Potentially Explosive Atmospheres In Accordance With Atex And Iecex; Ex Marking; Transmitter - ABB TTF300 Manual

Field-mount temperature transmitter
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

6
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | CI/TTF300-EN REV. H

2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx

Ex marking

Note
Further information on the approval of devices for use in potentially explosive atmospheres can be found in the explosion
protection test certificates (at www.abb.com/temperature).
Depending on the design, a specific marking in accordance with ATEX or IECEx applies.
A list of standards, including the output data to which the device conforms, can be found in the examination certificate or
manufacturer's declaration supplied with the device.
In devices with several types of protection, for example TTF300 -E4, observe the 'Product Identification' chapter in the operating
or commissioning instruction before commissioning.

Transmitter

ATEX intrinsic safety
The device fulfills the requirements of Directive 2014/34/EU in
case of corresponding purchase orders and is approved for use
in Zone 0, 1 and 2.
Model TTF300-E1H
To HW rev. 01.07:
Type Examination Test Certificate
From HW rev. 02.00:
Type Examination Test Certificate
Model TTF300-E1P and TTF300-E1F
Type Examination Test Certificate
II 1 G
Ex ia IIC T6...T1 Ga
II 2 (1) G
Ex [ia IIC Ga] ib IIC T6...T1 Gb
II 2 G (1D) Ex [ia IIIC Da] ib IIC T6...T1 Gb
ATEX increased safety and dust explosion protection
Approved for use in zone 2 and 22.
Model TTF300-E5
TTF300-E5H to HW rev. 01.07, TTF300-E5P, TTF300-E5F:
Manufacturer's Declaration
II 3 G
Ex ec IIC T6...T1 Gc
II 3 D
Ex tc IIIB T133°C Dc
ATEX dust explosion protection
Approved for use in Zone 21 and 22.
TTF300-D5H model to HW rev. 01.07
Type Examination Test Certificate
II 2D
Ex tb IIIC T135°C Db
II 3D
Ex tc IIIC T135°C Dc
ATEX dust explosion protection | intrinsic safety
Permitted for zone 21, 22 | Zone 0, 1 and 2.
The 'D6H' coding combines 'Dust explosion protection' (TTF300-
D5H) and 'Intrinsic safety' (TTF300-E1H) types of protection.
Devices with several types of protection may only be operated in
one of the possible types of protection. For this purpose,
PTB 05 ATEX 2017 X
observe the 'Product Identification' chapter in the operating or
commissioning instruction before commissioning.
PTB 20 ATEX 2008 X
TTF300-D6H model to HW rev. 01.07
Type examination test certificate
PTB 09 ATEX 2016 X
"Dust explosion protection", (TTF300-D5H)
Type examination certificate
"Intrinsic safety", (TTF300-E1H)
II 1G
II 2D
ATEX flameproof (enclosure)
Approved for use in Zone 1 and 2.
Model TTF300-E3
Type Examination Test Certificate
II 1/2 G
BVS 06 ATEX E 029
Ex ia IIC T6...T1 Ga
Ex tb IIIC T135°C Db
Ex db IIC T6/T4 Ga/Gb
BVS 06 ATEX E 029
PTB 05 ATEX 2017 X
PTB 99 ATEX 1144 X