RELAY
The relay can be used either for a high alarm, a low alarm or counter in flow mode. The difference is that a high alarm
has its reset below the set point, and a low alarm has its reset above the set point. The counter will output a pulse every
time a certain value is reached from the totaliser, which increments by more than a user defined value when in flow mode.
DEFAULT Off
SET POINT
This is the distance value whereby the relay will set.
DEFAULT 0 m
RESET POINT
This is the distance value whereby the relay will reset.
DEFAULT 0 m
PUMP CYCLE
Not applicable on this instrument
COUNT VALUE
Choose a value where the relay will pulse between 1-1000000 when in Flow mode.
DEFAULT 1000
CLEAR RELAY
Clears the number of cycles as well as the run hours recorded.
DEFAULT No
SETUP LINEARISER
This prompt will allow you to input a curve to linearise the flume. The span is divided by 21 and you can input the new
height for each point as well as the corresponding percentage fill at that point. KSONIK MICRO prompts you at each
point.
DEFAULT No
ACTIVATE
This function activates the lineariser.
DEFAULT Yes
SET POINT
This is the number at which point the user is inputting a linearised point.
HEIGHT/PERCENTAGE
Height is the distance of the flume from the bottom to a point where a suitable percentage volume can be determined.
DEFAULT 0.00 m
Enter the percentage volume of flume at a corresponding distance away from the bottom of the vessel or flume.
DEFAULT 0.00%
Operation instruction manual | KSONIK MICRO Ultrasonic Level Transmitter 17