Configuration Flow - ABB KSONIK MICRO Operation & Instruction Manual

Ultrasonic level transmitter
Table of Contents

Advertisement

8.2

CONFIGURATION FLOW

BASIC
SECURITY CODE
MODE
UNITS
EMPTY DISTANCE
SPAN
BLANKING
RATE OF CHANGE
APPLICATION
FACTORY RESET
TEMPERATURE COMPENSATION
SIMULATE
SET PASSWORD
BACKLIGHT
LOSSTIME
FAILSAFE
FAILSAFE
FLOW UNITS
MAXIMUM VALUE
ZERO OFF SET
TOTALISER COUNT
TOTALISER UNITS
TOTALISER RESET
FLOW CURVE
SETUP RELAY
RELAY
SETPOINT
RESET POINT
PUMP CYCLE
COUNT VALUE
CLEAR RELAY
SETUP LINEARISER
ACTIVATE LINEARISER
SETPOINT
HEIGHT
PERCENTAGE
14 KSONIK MICRO Ultrasonic Level Transmitter | Operation instruction manual
FLOW MODE
OPTIONS
0-9999
DISTANCE/LEVEL/FLOW
METERS/FEET
0.4-15.0 m
0.1-15.0 m
0.3-14.90 m
0.01-20.0 m/min
LIQUIDS/SOLIDS
NO/YES
ON/OFF
NO/YES
NO/YES
OFF/ON (1-60MIN)/PERM
30-900SEC
3.6mA, 4.0mA, 20mA, 21mA, Hold
SEE LIST
1-99999
-50 mm TO 50 mm
1-1000000
A-Z, a-z, 0-9
NO/YES
SEE LIST
NO/YES
OFF/LO/HI/COUNTER
SPAN
SPAN
OFF/FIFO/ROTATE
1-1000000
NO/YES
NO/YES
NO/YES
1-21
0m-SPAN
0-100%
DEFAULTS
5159
DISTANCE
METERS
2 m
1.5 m
0.50 m
0.50 m/min
LIQUIDS
NO
OFF
NO
NO
2MIN
300SEC
Hold
LT/SEC
1000
0 mm
1
Lt
NO
V-NOTCH
NO
OFF
0 m
0 m
NO
1000
NO
NO
YES
1
0 m
0%