WAGO 750-462 Series Manual page 14

Fieldbus independent i/o modules, 2 ai thermocouple
Table of Contents

Advertisement

14 •
750-462 (/xxx-xxx) [2 AI Thermocouple]
Process Image
Temperature
Temperature
<ca.-100.1
1)
°C
<-50.0
'1111.1110.0000.1100'
-50.0
'1111.1110.0000.1100'
0.0
'0000.0000.0000.0000'
100.0
'0000.0011.1110.1000'
200.0
'0000.0111.1101.0000'
300.0
'0000.1011.1011.1000'
400.0
'0000.1111.1010.0000'
500.0
'0001.0011.1000.1000'
1000.0
'0010.0111.0001.0000'
1500.0
'0011.1010.1001.1000'
1700.0
'0100.0010.0110.1000'
>1700.0
'0100.0010.0110.1000'
°C
'1111.1100.0001.0111'
-100.0
'1111.1100.0001.1000'
-50.0
'1111.1110.0000.1100'
0.0
'0000.0000.0000.0000'
50.0
'0000.0001.1111.0100'
100.0
'0000.0011.1110.1000'
150.0
'0000.0101.1101.1100'
200.0
'0000.0111.1101.0000'
250.0
'0000.1001.1100.0100'
300.0
'0000.1011.1011.1000'
350.0
'0000.1101.1010.1100'
400.0
'0000.1111.1010.0000'
>400.0
'0000.1111.1010.0000'
Temperature values below 0 °C are represented in two's complement binary form.
750-462/000-001, Type S
Numerical value
binary
hex.
0xFE0C
0xFE0C
0x0000
0x03E8
0x07D0
0x0BB8
0x0FA0
0x1388
0x2710
0x3A98
0x4268
>0x4268
750-462/000-002, Type T
1)
Numerical value
binary
hex.
0xFC17
0xFC18
0xFE0C
0x0000
0x01F4
0x03E8
0x05DC
0x07D0
0x09C4
0x0BB8
0x0DAC
0x0FA0
>0x0FA0
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
-500
0x41
on
-500
0x41
off
0
0x00
off
1000
0x00
off
2000
0x00
off
3000
0x00
off
4000
0x00
off
5000
0x00
off
10000
0x00
off
15000
0x00
off
17000
0x00
off
>17000
0x42
on
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
-1001
0x41
on
-1000
0x00
off
-500
0x00
off
0
0x00
off
500
0x00
off
1000
0x00
off
1500
0x00
off
2000
0x00
off
2500
0x00
off
3000
0x00
off
3500
0x00
off
4000
0x42
on
>4000
0x42
on