Temperature
1)
Temperature
WAGO-I/O-SYSTEM 750
I/O Modules
°C
<-100.0
'1111.1100.0001.1000'
-100.0
'1111.1100.0001.1000'
0.0
'0000.0000.0000.0000'
100.0
'0000.0011.1110.1000'
200.0
'0000.0111.1101.0000'
300.0
'0000.1011.1011.1000'
400.0
'0000.1111.1010.0000'
500.0
'0001.0011.1000.1000'
1000.0
'0010.0111.0001.0000'
1200.0
'0010.1110.1110.0000'
>1200.0
'0010.1110.1110.0000'
Temperature values below 0 °C are represented in two's complement binary form.
°C
<600.0
'0001.0111.0111.0000'
600.0
'0001.0111.0111.0000'
700.0
'0001.1011.0101.1000'
800.0
'0001.1111.0100.0000'
900.0
'0010.0011.0010.1000'
1000.0
'0010.0111.0001.0000'
1500.0
'0011.1010.1001.1000'
1600.0
'0011.1110.1000.0000'
1700.0
'0100.0010.0110.1000'
1800.0
'0100.0110.0101.0000'
>1800.0
'0100.0110.0101.0000'
750-462 (/xxx-xxx) [2 AI Thermocouple] • 15
750-462/000-006, Type J
1)
Numerical value
binary
hex.
0xFC18
0xFC18
0x0000
0x03E8
0x07D0
0x0BB8
0x0FA0
0x1388
0x2710
0x2EE0
>0x2EE0 >12000
750-462/000-007, Type B
Numerical value
binary
hex.
0x1770
0x1770
0x1B58
0x1F40
0x2328
0x2710
0x3A98
0x3E80
0x4268
0x4650
>0x4650
Process Image
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
-1000
0x41
on
-1000
0x00
off
0
0x00
off
1000
0x00
off
2000
0x00
off
3000
0x00
off
4000
0x00
off
5000
0x00
off
10000
0x00
off
12000
0x00
off
0x42
on
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
6000
0x41
on
6000
0x00
off
7000
0x00
off
8000
0x00
off
9000
0x00
off
10000
0x00
off
15000
0x00
off
16000
0x00
off
17000
0x00
off
18000
0x00
off
>18000
0x42
on