10 •
750-468 [4 AI DC 0-10 V, Single-Ended]

Technical Data

2.1.1.6 Technical Data
Module Specific Data
Number of inputs
Voltage supply
Current consumption
Input voltage
Signal voltage
Internal resistance
Resolution
Conversion time
Measuring error
Temperature coefficient
Isolation
Bit width
Dimensions (mm) W x H x L
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
EMC-Emission of interference (CE)
EMC-Immunity to interference
(Ship building)
EMC-Emission of interference
(Ship building)
(internal)
typ.
max.
typ.
typ.
25 °C
4
via system voltage DC /DC
60 mA
35 V
0 V... 10 V
133 kΩ
12 Bit
4 ms
<± 0.2 % of the full scale value
<± 0.01 % /K of the full scale value
500 V (System/Supply)
4 x 16 bits data
4 x 8 bits control / status (option)
12 x 64* x 100
* from upper edge of 35 DIN rail
ca. 55 g
acc. to EN 50082-2 (96)
acc. to EN 50081-1 (93)
acc. to Germanischer Lloyd (97)
acc. to Germanischer Lloyd (97)
WAGO-I/O-SYSTEM 750
I/O Modules