Notes On Use With Inductive Loads And Transformers - gefran GPC 40-600A Use And Installation Manual

Advanced power controllers
Table of Contents

Advertisement

3.8.

Notes on use with inductive loads and transformers

When the GPC controller is in operation, it is NOT
permissible to disconnect the connection between the
GPC and the transformer or between the transformer
and the load.
The maximum current that can be controlled by the
GPC is reduced compared to the nominal value of the
device (see technical specifications).
In ZC and BF trigger modes use the delay-triggering
function to limit the peak magnetising current.
In PA trigger mode use softstart function
DO NOT use the HSC trigger mode.
Do not connect RC snubbers in parallel to the trans-
former primary.
Always set DIP switch No. 5 to ON (and carry out the
initial configuration procedure described in paragraph
"1.6.2. Initialisation procedure and loading of default
values").