Connection Example For Two-Phase Gpc (2Ph) For 2 Independent Single-Phase Loads - gefran GPC 40-600A Use And Installation Manual

Advanced power controllers
Table of Contents

Advertisement

3.7.3.
Connection example for two-phase GPC (2PH) for 2 independent single-phase
loads
L1
L2
L3
N
(*)
FUSE
(**)
J7
GG FUSE
(**) = Connection only required with Vload input option
(control option = 3 and 4)
L
L
L /N
L /N
y
x
y
x
X = Y
X,Y = 1,2,3
(*)
GG FUSE
B A
J6
J7
J6
1/L1
1/L1
GPC-E1
GPC-M
2/T1
2/T1
PE
A
R
R
Load 2
Load 1
B
81900A "MHW_GPC-40/600A"_03-2021_ENG_page 57
Two single-phase loads can also be connected to different supply
lines, line to line or line and neutral.
Different power levels can be managed for each of the two loads.
Lx
FUSE
Id
2
1/L1
V2
GPC-E1
2/T1
R2
GG FUSE
Ly/N
Id =
V
P
Id
FIRING MODE ZC, BF, HSC, PA
HB DIAGNOSTICS
Partial and total load break for each individual branch
AVAILABLE
Ultra-rapid fuse only required for controls with
Fuse
option Fuse = 0
GG fuse
See fuse sections
Lx
Id
1
1/L1
V1
2/T1
GG FUSE
Ly/N
P
V × cos φ
CAUTION
(*) : Take care to connect
terminals 1/L1 and 3/L1
to the same phase
GPC - DIP switch configuration
DIP 1
DIP 2
DIP 3
DIP 4
OFF
OFF
OFF
OFF
Phase / phase-to-phase voltage (Lx - Ly / N)
Single-phase single load power
load current if resistive load cos φ=1
FUSE
GPC-M
R1
DIP 5
OFF