Diagnostics
Energy calculation
Type of connection and
controllable load
(selection via DIP switch)
FUNCTIONS
General
Current reading
Voltage reading
Visualisation
Counter reset
with GPC-M only
with GPC-M + GPC-E1
with GPC-M + GPC-E1 +
GPC-E2
81900A "MHW_GPC-40/600A"_03-2021_ENG_page 90
Timed softstart ramp, with or without peak current
control.
Softstart ramp, specifically for infrared lamps.
Time-controlled switch-off ramp.
RMS load current limitation.
Delay-Triggering 0-90° for firing inductive loads in ZC
and BF mode.
SCR short circuit (current presence with OFF command).
No line voltage.
No fan power supply.
No current due to open SCR/disconnected load.
Over-temperature alarm (from the power module, power
cable terminals or fuse).
HB alarm from an interrupted or partially interrupted
load.
Automatic calibration of the HB alarm threshold based
on the current level in the load.
Load short circuit or overcurrent alarm
Three-phase line unbalanced.
Incorrect phase rotation in three-phase load configura-
tion.
Total energy value supplied to load with local display via
terminal and remote acquisition via fieldbus
Local via terminal or remote acquisition via fieldbus.
Yes
1 single-phase load
2 single-phase loads, or
only in ZC and BF trigger modes:
1 three-phase closed delta load controlled on two phases,
or
1 three-phase star load without neutral controlled on two
phases
3 single-phase loads, or
3 independent single-phase open delta loads, or
1 three-phase open delta load, or
1 three-phase closed delta load, or
1 three-phase star load with neutral, or
1 three-phase star load without neutral