Front Panel; Fuse; Fig. 8-5: Female Connector Strip Is Plugged On - Bosch Rexroth IndraControl VCP 02.2 Project Planning Manual

Table of Contents

Advertisement

R911310375 / 02 | Rexroth IndraControl VCP 02
Maintenance and Installation
8.7

Front Panel

8.8

Fuse

Electric Drives and Controls | Bosch Rexroth AG
3. Plug the female connector strip onto connector X1.

Fig. 8-5: Female connector strip is plugged on

4. Secure the female connector strip in place with a screw-type locking
to prevent it from slipping out.
A separate conductor must always be provided for the protective
grounding at the threaded bolt. The conductor must have a minimum
cross-section of 1.5 mm² (16 AWG) and must be kept as short as pos-
sible.
Only use a damp cloth to remove any dirt from the front panel.
The semiconductor fuse cannot be replaced!
A semiconductor fuse is used to protect the device. Once the fuse has
been tripped, the device must be disconnected from the supply voltage
to allow the semiconductor fuse to regenerate. At an ambient tempera-
ture of 20 °C (68° F), the regeneration takes approximately 20 sec-
onds. The higher the ambient temperature, the longer the regeneration
takes.