PAR. DESCRIPTION
Temperature control setpoint SP1. The SEtpoint is visible from the
SP1
machine status menu and not from the programming menu.
Temperature control setpoint SP2. The SEtpoint is visible from the
SP2
machine status menu and not from the programming menu.
CONTROLLER 1 (folder 'rE1')
This sets the controller 1 operating mode.
HC1
H (0) = Hot; C (1) = Cold.
OS1 Temperature value to be added to SP1 if reduced set enabled
Operating band 1.
db1
(See 'ON/OFF regulation diagram')
OUT1 activation differential.
dF1
The utility stops on reaching the SP1 value (as indicated by control probe) and
restarts at a temperature value equal to T=SP1+dF1 relative to HC1.
HS1 Maximum value assignable to setpoint SP1.
LS1 Minimum value assignable to setpoint SP1.
Maximum temperature alarm on OUT1.
HA1
(See 'Max/Min temperature alarms')
PARAMETERS TABLE
MODEL
RANGE
VALUE M.U. LEVEL
NTC/PTC
PT100-Tc
LS1...HS1
V/I
NTC/PTC
PT100-Tc
LS2...HS2
V/I
ALL
H/C
NTC/PTC
-30.0...30.0
PT100-Tc
-30.0...30.0
V/I
-30...30
NTC/PTC
0.0...30.0
PT100-Tc
0.0...30.0
V/I
0...30
NTC/PTC
0.0...30.0
PT100-Tc
0.0...30.0
V/I
0...30
NTC/PTC
PT100-Tc
LS1...HdL
V/I
NTC/PTC
PT100-Tc
LdL...HS1
V/I
NTC/PTC
LA1...150.0
PT100-Tc
LA1...1999
V/I
LA1...150
0.0
°C/°F
0.0
°C/°F
0
num
0.0
°C/°F
0.0
°C/°F
0
num
H
flag
Inst
0.0
°C/°F
0.0
°C/°F
Inst
0
num
1.0
°C/°F
1.0
°C/°F
Inst
1
num
1.0
°C/°F
1.0
°C/°F
User/Inst
1
num
140.0
°C/°F
1350
°C/°F
User/Inst
199
num
-50.0
°C/°F
-199.9
°C/°F
User/Inst
-199
num
140.0
°C/°F
1350
°C/°F
User/Inst
150
num
Need help?
Do you have a question about the ICPlus 915 and is the answer not in the manual?
Questions and answers