Parameters Table - Eliwell ICPlus 902 Manual

Electronic controller with 1 intervention point
Table of Contents

Advertisement

PAR. DESCRIPTION
Temperature control setpoint SP1. The SEtpoint is visible from the
SP1
machine status menu and not from the programming menu.
CONTROLLER 1 (folder 'rE1')
This sets the controller 1 operating mode.
HC1
H (0) = Hot; C (1) = Cold.
OS1 Temperature value to be added to SP1 if reduced set enabled
OUT1 activation differential.
dF1
The utility stops on reaching the SP1 value (as indicated by control probe) and
restarts at a temperature value equal to T=SP1+dF1 relative to HC1.
HS1 Maximum value assignable to setpoint SP1.
LS1 Minimum value assignable to setpoint SP1.
Maximum temperature alarm on OUT1.
HA1
(See 'Max/Min temperature alarms')
Minimum temperature alarm on OUT1.
LA1
(See 'Max/Min temperature alarms')
Switch-on delay. The indicated time must elapse between the request for
dn1
activation of the controller 1 relay and switch-on. 0 = not active.

PARAMETERS TABLE

MODEL
RANGE
VALUE M.U. LEVEL
NTC/PTC
PT100-Tc
LS1...HS1
V/I
ALL
H/C
NTC/PTC
-30.0...30.0
PT100-Tc
-30.0...30.0
V/I
-30...30
NTC/PTC
0.0...30.0
PT100-Tc
0.0...30.0
V/I
0...30
NTC/PTC
PT100-Tc
LS1...HdL
V/I
NTC/PTC
PT100-Tc
LdL...HS1
-199.9
V/I
NTC/PTC
LA1...150.0
PT100-Tc
LA1...1999
V/I
LA1...150
NTC/PTC
-150.0...HA1
PT100-Tc
-328...HA1
-199.9
V/I
-150...HA1
ALL
0...250
0.0
°C/°F
0.0
°C/°F
0
num
H
flag
Inst
0.0
°C/°F
0.0
°C/°F
Inst
0
num
1.0
°C/°F
1.0
°C/°F
User/Inst
1
num
140.0
°C/°F
1350
°C/°F
User/Inst
199
num
-50.0
°C/°F
°C/°F
User/Inst
-199
num
140.0
°C/°F
1350
°C/°F
Inst
150
num
-50.0
°C/°F
°C/°F
Inst
-150
num
0
min
Inst