Toshiba GRL150-100 Series Instruction Manual page 96

Line differential relay
Table of Contents

Advertisement

H D L C
I E C
• Enter the relay address number on "HDLC" line for RSM or "IEC" line for IEC60870-5-103
and press the ENTER key.
CAUTION
Do not overlap the relay address number.
• Select "Switch" on the "Comms" screen to select the protocol and transmission speed (baud
rate), etc., of the RSM and IEC60870-5-103.
/ 3
P r o t o c o l
H D L C / I E C
2 3 2 C
9 . 6 / 1 9 . 2 / 5 7 . 6
I E C B R
9 . 6 / 1 9 . 2
I E C B L K
N o r m a l / B l o c k e d
• Select the number and press the ENTER key.
<Protocol>
This setting is for changing the protocol (HDLC or IEC) of the channel 1 (COM1 port). In the
model with two channels (COM1 and COM2 ports), this setting for COM1 should be "HDLC".
• When the remote RSM system applied, select 0(=HDLC). When the IEC60870-5-103 applied,
select 1(=IEC103).
CAUTION
When changing the setting to the HDLC during the IEC103 operation, the
IEC103 command INF18 in Appendix M is canceled.
The output of IEC103 command INF18 can be observed by assigning their
signal numbers to LEDs or binary output relays (see Sections 4.2.6.9 and
4.2.6.10).
<232C>
This line is to select the RS-232C baud rate when the RSM system applied.
Note: The default setting of the 232C is 9.6kbps. The 57.6kbps setting, if possible, is recommended to
serve user for comfortable operation. The setting of RSM100 is also set to the same baud rate.
<IECBR>
This line is to select the baud rate when the IEC60870-5-103 system applied.
<IECBLK>
Enter 1(=Blocked) to block the monitor direction in the IEC60870-5-103 communication.
4.2.6.5
Setting the Recording
To set the recording function as described in Section 4.2.3, do the following:
• Select "Set.(change)" on the main "MENU" screen to display the "Set.(change)" screen.
1
_
2
S w i t c h
.
0
0
1
0
95
_
6 F 2 S 0 8 2 8