Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored
Recording time
50Hz
60Hz
Settings
The elements necessary for initiating a disturbance recording and their setting ranges are shown
in the table below.
Element
Range
OC
0.5-250.0 A
(0.10-50.00 A
EF
0.5-250.0 A
(0.10-50.00 A
SEF
0.01-1.00 A
(0.002-0.200 A
(*) Current values shown in the parentheses are for the case of a 1A rating. Other current values are
for the case of a 5A rating.
Starting the disturbance recording by a tripping command or the starter element listed above is
enabled or disabled by setting the following scheme switches.
Element
Range
[Trip]
OFF/ON
[OC]
OFF/ON
[EF]
OFF/ON
[SEF]
OFF/ON
0.1s
0.5s
1.0s
1.5s
40
25
15
10
40
20
10
9
Step
Default
0.1 A
10.0 A
0.01 A
2.00 A) (*)
0.1 A
3.0 A
0.01 A
0.60A)
0.01 A
1.00 A
0.001 A
0.200 A)
Step
Default
ON
ON
ON
ON
⎯
68
2.0s
2.5s
3.0s
9
7
6
7
6
5
Remarks
Overcurrent detection
Earth fault detection
Sensitive earth fault detection
Remarks
Start by tripping command
Start by OC operation
Start by EF operation
Start by SEF operation
⎯