Toshiba GRL150-100 Series Instruction Manual page 69

Line differential relay
Table of Contents

Advertisement

Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored
Recording time
50Hz
60Hz
Settings
The elements necessary for initiating a disturbance recording and their setting ranges are shown
in the table below.
Element
Range
OC
0.5-250.0 A
(0.10-50.00 A
EF
0.5-250.0 A
(0.10-50.00 A
SEF
0.01-1.00 A
(0.002-0.200 A
(*) Current values shown in the parentheses are for the case of a 1A rating. Other current values are
for the case of a 5A rating.
Starting the disturbance recording by a tripping command or the starter element listed above is
enabled or disabled by setting the following scheme switches.
Element
Range
[Trip]
OFF/ON
[OC]
OFF/ON
[EF]
OFF/ON
[SEF]
OFF/ON
0.1s
0.5s
1.0s
1.5s
40
25
15
10
40
20
10
9
Step
Default
0.1 A
10.0 A
0.01 A
2.00 A) (*)
0.1 A
3.0 A
0.01 A
0.60A)
0.01 A
1.00 A
0.001 A
0.200 A)
Step
Default
ON
ON
ON
ON
68
2.0s
2.5s
3.0s
9
7
6
7
6
5
Remarks
Overcurrent detection
Earth fault detection
Sensitive earth fault detection
Remarks
Start by tripping command
Start by OC operation
Start by EF operation
Start by SEF operation
6 F 2 S 0 8 2 8