Toshiba GRL150-100 Series Instruction Manual page 121

Line differential relay
Table of Contents

Advertisement

4.2.7.2
Binary Output Relay
It is possible to forcibly operate all binary output relays for checking connections with the external
devices. Forced operation can be performed on one or more binary outputs at a time.
• Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. Then the LCD
displays the name of the output relay.
/ 2
T P 1
D i s a b l e / E n a b l e
T P 2
D i s a b l e / E n a b l e
B O 1
D i s a b l e / E n a b l e
B O 2
D i s a b l e / E n a b l e
B O 3
D i s a b l e / E n a b l e
B O 4
D i s a b l e / E n a b l e
B O 5
D i s a b l e / E n a b l e
F A I L
D i s a b l e / E n a b l e
• Enter 1(=Enable) and press the ENTER key to operate the output relays forcibly.
• After completing the entries, press the END key. Then the LCD displays the screen shown
below.
O p e r a t e ?
E N T E R = Y
• Keep pressing the ENTER key to operate the assigned output relays.
• Release pressing the ENTER key to reset the operation.
• Press the CANCEL key to return to the upper "Binary O/P" screen.
4.2.7.3
Logic Circuit
It is possible to observe the binary signal level on the signals listed in Appendix B with monitoring
jacks A and B.
• Select "Logic circuit" on the "Test" screen to display the "Logic circuit" screen.
/ 2
T e r m A
T e r m B
• Enter a signal number to be observed at monitoring jack A and press the ENTER key.
• Enter the other signal number to be observed at monitoring jack B and press the ENTER key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
B i n a r y
O / P
0
0
0
0
0
0
0
C A N C E L = N
L o g i c
c i r c u i t
1
_
4 8
_
120
_
6 F 2 S 0 8 2 8