Toshiba GRL150-100 Series Instruction Manual page 208

Line differential relay
Table of Contents

Advertisement

Setting 2
No.
Name
5A rating
1 Passwd
Setting Password
2 Notes
Plant name
3 Des.
Description
4 Com.
HDLC
5
IEC
6
Protocol
7
232C
8
IECBR
9
IECBLK
Normal / Blocked
10 Record
BITRN
11
Time
12
OC
0.1 - 250.0
13
EF
0.1 - 250.0
14
SEF
0.01 - 1.00
15
Trip
16
OC
17
EF
18
SEF
19
SIG1
20
SIG2
21
SIG3
22
SIG4
23
SIG5
24
SIG6
25
SIG7
26
SIG8
27
SIG9
28
SIG10
29
SIG11
30
SIG12
31
SIG13
32
SIG14
33
SIG15
34
SIG16
35
SIG17
36
SIG18
37
SIG19
38
SIG20
39
SIG21
40
SIG22
41
SIG23
42
SIG24
43
SIG25
44
SIG26
45
SIG27
46
SIG28
47
SIG29
48
SIG30
49
SIG31
50
SIG32
51
TCSPEN
Off / On / Opt-On
CBSMEN
52
53
DSSMEN
54
TCAEN
ΣI^yAEN
55
56
OPTAEN
57
FERAEN
58
TCALM
ΣI^yALM
59
60
YVALUE
61
OPTALM
62
CF-PER
63
FERALM
Range
Units
Contents
1A rating
-
--
Password for Setting menu
-
--
Plant name
-
--
Description
1 - 32
--
Address for RSM 100
0 - 254
--
Address for IEC103
HDLC / IEC
--
Switch for communications
9.6 / 19.2 / 57.6
--
ditto
9.6 / 19.2
--
ditto
--
ditto
0 - 128
--
Number of bi-trigger (on/off) events
0.1 - 3.0
s
Record time
0.02 - 50.00
A
OC
0.02 - 50.00
A
EF
0.002 - 0.200
A
SEF
Off / On
--
Disturbance trigger Trip
Off / On
--
Disturbance trigger OC
Off / On
--
Disturbance trigger EF
Off / On
--
Disturbance trigger SEF
0 - 3071
--
Disturbance record binary signal #1
0 - 3071
--
Disturbance record binary signal #2
0 - 3071
--
Disturbance record binary signal #3
0 - 3071
--
Disturbance record binary signal #4
0 - 3071
--
Disturbance record binary signal #5
0 - 3071
--
Disturbance record binary signal #6
0 - 3071
--
Disturbance record binary signal #7
0 - 3071
--
Disturbance record binary signal #8
0 - 3071
--
Disturbance record binary signal #9
0 - 3071
--
Disturbance record binary signal #10
0 - 3071
--
Disturbance record binary signal #11
0 - 3071
--
Disturbance record binary signal #12
0 - 3071
--
Disturbance record binary signal #13
0 - 3071
--
Disturbance record binary signal #14
0 - 3071
--
Disturbance record binary signal #15
0 - 3071
--
Disturbance record binary signal #16
0 - 3071
--
Disturbance record binary signal #17
0 - 3071
--
Disturbance record binary signal #18
0 - 3071
--
Disturbance record binary signal #19
0 - 3071
--
Disturbance record binary signal #20
0 - 3071
--
Disturbance record binary signal #21
0 - 3071
--
Disturbance record binary signal #22
0 - 3071
--
Disturbance record binary signal #23
0 - 3071
--
Disturbance record binary signal #24
0 - 3071
--
Disturbance record binary signal #25
0 - 3071
--
Disturbance record binary signal #26
0 - 3071
--
Disturbance record binary signal #27
0 - 3071
--
Disturbance record binary signal #28
0 - 3071
--
Disturbance record binary signal #29
0 - 3071
--
Disturbance record binary signal #30
0 - 3071
--
Disturbance record binary signal #31
0 - 3071
--
Disturbance record binary signal #32
--
Trip Circuit Supervision Enable
Off / On
--
CB condition super visor enable
Off / On
--
DS condition super visor enable
Off / On
--
Trip CounterAlarm Enable
Off / On
--
ΣI^y Alarm Enable
Off / On
--
Operate Time Alarm Enable
Off / On
--
Frame error rate alarm enable
1 - 10000
--
Trip Count Alarm Threshold
10 - 10000
E6
ΣI^y Alarm
1.0 - 2.0
--
Y value
100 - 5000
ms
Operate Time Alarm Threshold
1 - 60
s
CF period threshold
0.0 - 50.0
%
Default Setting of Relay Series(5A rating / 1A rating)
Model1
100
110
--
3.0 / 0.60
--
--
On
--
Refer to the "GRL150(Disturbance)"sheet.
⎯ 207 ⎯
6 F 2 S 0 8 2 8
Model2
120
400
410
420
0000
no-name
no-data
1
2
HDLC
9.6
19.2
Normal
100
2.0
10.0 / 2.00
--
--
3.0 / 0.60
--
1.00 / 0.200
--
1.00 / 0.200
On
On
--
--
On
--
On
--
On
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
Off
Off
Off
Off
Off
Off
Off
10000
10000
2.0
1000
10
20.0
User
Setting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl150-400 seriesGrl150-100a-10-10

Table of Contents