2.10.2 Setting
The setting elements necessary for the cold load protection and their setting ranges are as follows:
Element
ICLDO
TCLE
TCLR
TCLDO
[CLEN]
[CLDOEN]
DIFI1
DIFI2
OC1
OC2
OC3
OC4
OC5
EF1
EF2
EF3
EF4
SE1
SE2
SE3
SE4
BCD
(*) Current values shown in the parentheses are in the case of a 1 A rating. Other current values
are in the case of a 5 A rating.
Range
Step
0.5 – 10.0 A
0.1 A
(0.10 - 2.00 A)(*)
(0.01 A)
0-10000 s
1 s
0-10000 s
1 s
0.00-100.00 s
0.01 s
Off / On
Off / On
0.50 − 10.00A
0.01A
(0.10 − 2.00A
0.01A
1.0 − 120.0A
0.1A
(0.2 − 24.0A
0.1A
0.1 – 25.0 A
0.1 A
(0.02 – 5.00 A)(*)
(0.01 A)
0.1 – 25.0 A
0.1 A
(0.02 – 5.00 A)(*)
(0.01 A)
0.1 – 250.0 A
0.1 A
(0.02 – 50.00 A)(*)
(0.01 A)
0.1 – 250.0 A
0.1 A
(0.02 – 50.00 A)(*)
(0.01 A)
0.1 – 250.0 A
0.1 A
(0.02 – 50.00 A)(*)
(0.01 A)
0.1 – 25.0 A
0.01 A
(0.02 – 5.00 A)
(0.01 A)
0.1 – 25.0 A
0.01 A
(0.02 – 5.00 A)
(0.01 A)
0.1 – 250.0 A
0.1 A
(0.02 – 50.00 A)(*)
(0.01 A)
0.1 – 250.0 A
0.1 A
(0.02 – 50.00 A)(*)
(0.01 A)
0.025 – 0.125 A
0.001 A
(0.005 – 0.025 A)(*)
(0.001 A)
0.025 – 0.125 A
0.001 A
(0.005 – 0.025 A)(*)
(0.001 A)
0.025 – 0.125 A
0.001 A
(0.005 – 0.025 A)(*)
(0.001 A)
0.025 – 0.125 A
0.001 A
(0.005 – 0.025 A)(*)
(0.001 A)
0.10 – 1.00
0.01
⎯ 48 ⎯
Default
Remarks
2.5 A
Cold load drop-off threshold setting
(0.50 A)
100 s
Cold load enable timer
100 s
Cold load reset timer
0.00 s
Cold load drop-off timer
Off
Cold load protection enable
Off
Cold load drop-off enable
10.00A
Small current region
2.00A)(*1)
30.0A
Large current region
6.0A)
10.0 A
OC1 threshold setting
(2.00 A)
25.0 A
OC2 threshold setting
(5.00 A)
100.0 A
OC3 threshold setting
(20.00 A)
200.0 A
OC4 threshold setting
(40.00 A)
20.0 A
OC5 threshold setting
(4.00 A)
10.0 A
EF1 threshold setting
(2.00 A)
25.0 A
EF2 threshold setting
(5.00 A)
100.0 A
EF3 threshold setting
(20.00 A)
200.0 A
EF4 threshold setting
(40.00 A)
0.100 A
SEF1 threshold setting
(0.020 A)
0.100 A
SEF2 threshold setting
(0.020 A)
0.100 A
SEF3 threshold setting
(0.020 A)
0.100 A
SEF4 threshold setting
(0.020 A)
0.20
I
/ I
2
1
6 F 2 S 0 8 2 8